🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 0.49%
Aluminum Wire (≤3% Drop)4 AWGDrop: 1.22V (0.51%)
Voltage at Load End238.8 VLoss: 1.18 V (70.6 W)
Power & Breaker (125%)14.4 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.53 V (3.14%)232.5 V12.41 V (5.17%)451.6 WDrop/Amp High
12 AWG3.31 mm²20 A4.73 V (1.97%)235.3 V7.8 V (3.25%)283.8 WDrop/Amp High
10 AWG5.26 mm²30 A2.98 V (1.24%)237.0 V4.91 V (2.05%)178.6 WDrop/Amp High
8 AWG8.37 mm²50 A1.87 V (0.78%)238.1 V3.09 V (1.29%)112.2 WDrop/Amp High
6 AWG13.3 mm²65 A1.18 V (0.49%)238.8 V1.94 V (0.81%)70.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.74 V (0.31%)239.3 V1.22 V (0.51%)44.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.59 V (0.24%)239.4 V0.97 V (0.4%)35.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.47 V (0.19%)239.5 V0.77 V (0.32%)27.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.37 V (0.15%)239.6 V0.61 V (0.25%)22.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.29 V (0.12%)239.7 V0.48 V (0.2%)17.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.23 V (0.1%)239.8 V0.38 V (0.16%)13.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.18 V (0.08%)239.8 V0.3 V (0.13%)11.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (0.06%)239.9 V0.24 V (0.1%)8.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (0.05%)239.9 V0.2 V (0.08%)7.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.04%)239.9 V0.17 V (0.07%)6.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.04%)239.9 V0.15 V (0.06%)5.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.03%)239.9 V0.13 V (0.05%)4.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.03%)239.9 V0.1 V (0.04%)3.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.02%)239.9 V0.08 V (0.04%)3.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.02%)240.0 V0.07 V (0.03%)2.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)240.0 V0.05 V (0.02%)1.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 20 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 1.18V (0.49%) and delivers 238.8V at the load.

What size aluminum wire is required for 60 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 1.22V (0.51%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.