🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 20 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.37V (0.08%)
Voltage at Load End479.8 VLoss: 0.22 V (193.1 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 20 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.32 V (11.32%)425.7 V89.6 V (18.67%)47038.8 WDrop/Amp High
12 AWG3.31 mm²20 A34.13 V (7.11%)445.9 V56.3 V (11.73%)29559.2 WDrop/Amp High
10 AWG5.26 mm²30 A21.48 V (4.47%)458.5 V35.43 V (7.38%)18600.9 WDrop/Amp High
8 AWG8.37 mm²50 A13.5 V (2.81%)466.5 V22.27 V (4.64%)11689.5 WDrop/Amp High
6 AWG13.3 mm²65 A8.49 V (1.77%)471.5 V14.01 V (2.92%)7356.5 WDrop/Amp High
4 AWG21.15 mm²85 A5.34 V (1.11%)474.7 V8.81 V (1.84%)4626.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.24 V (0.88%)475.8 V6.99 V (1.46%)3668.6 WDrop/Amp High
2 AWG33.62 mm²115 A3.36 V (0.7%)476.6 V5.54 V (1.15%)2910.2 WDrop/Amp High
1 AWG42.41 mm²130 A2.66 V (0.55%)477.3 V4.39 V (0.92%)2307.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.11 V (0.44%)477.9 V3.48 V (0.73%)1829.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.68 V (0.35%)478.3 V2.76 V (0.58%)1451.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.33 V (0.28%)478.7 V2.19 V (0.46%)1150.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.05 V (0.22%)478.9 V1.74 V (0.36%)912.7 WDrop/Amp High
250 kcmil126.7 mm²255 A0.89 V (0.19%)479.1 V1.47 V (0.31%)772.2 WDrop/Amp High
300 kcmil152.0 mm²285 A0.74 V (0.15%)479.3 V1.23 V (0.26%)643.7 WDrop/Amp High
350 kcmil177.3 mm²310 A0.64 V (0.13%)479.4 V1.05 V (0.22%)551.8 WDrop/Amp High
400 kcmil202.7 mm²335 A0.56 V (0.12%)479.4 V0.92 V (0.19%)482.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.45 V (0.09%)479.6 V0.74 V (0.15%)386.1 WDrop/Amp High
600 kcmil304.0 mm²420 A0.37 V (0.08%)479.6 V0.61 V (0.13%)321.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.3 V (0.06%)479.7 V0.49 V (0.1%)257.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.22 V (0.05%)479.8 V0.37 V (0.08%)193.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 20 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 20 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 0.22V (0.05%) and delivers 479.8V at the load.

What size aluminum wire is required for 500 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.37V (0.08%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.