🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.07%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.55V (0.11%)
Voltage at Load End479.7 VLoss: 0.33 V (289.6 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A81.47 V (16.97%)398.5 V134.39 V (28.0%)70558.3 WDrop/Amp High
12 AWG3.31 mm²20 A51.2 V (10.67%)428.8 V84.45 V (17.59%)44338.7 WDrop/Amp High
10 AWG5.26 mm²30 A32.22 V (6.71%)447.8 V53.14 V (11.07%)27901.4 WDrop/Amp High
8 AWG8.37 mm²50 A20.25 V (4.22%)459.8 V33.4 V (6.96%)17534.2 WDrop/Amp High
6 AWG13.3 mm²65 A12.74 V (2.65%)467.3 V21.02 V (4.38%)11034.7 WDrop/Amp High
4 AWG21.15 mm²85 A8.01 V (1.67%)472.0 V13.22 V (2.75%)6939.1 WDrop/Amp High
3 AWG26.67 mm²100 A6.35 V (1.32%)473.6 V10.48 V (2.18%)5502.9 WDrop/Amp High
2 AWG33.62 mm²115 A5.04 V (1.05%)475.0 V8.31 V (1.73%)4365.3 WDrop/Amp High
1 AWG42.41 mm²130 A4.0 V (0.83%)476.0 V6.59 V (1.37%)3460.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.17 V (0.66%)476.8 V5.23 V (1.09%)2743.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.51 V (0.52%)477.5 V4.15 V (0.86%)2176.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.99 V (0.42%)478.0 V3.29 V (0.69%)1726.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.58 V (0.33%)478.4 V2.61 V (0.54%)1369.0 WDrop/Amp High
250 kcmil126.7 mm²255 A1.34 V (0.28%)478.7 V2.21 V (0.46%)1158.3 WDrop/Amp High
300 kcmil152.0 mm²285 A1.11 V (0.23%)478.9 V1.84 V (0.38%)965.5 WDrop/Amp High
350 kcmil177.3 mm²310 A0.96 V (0.2%)479.0 V1.58 V (0.33%)827.8 WDrop/Amp High
400 kcmil202.7 mm²335 A0.84 V (0.17%)479.2 V1.38 V (0.29%)724.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.67 V (0.14%)479.3 V1.1 V (0.23%)579.2 WDrop/Amp High
600 kcmil304.0 mm²420 A0.56 V (0.12%)479.4 V0.92 V (0.19%)482.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.45 V (0.09%)479.6 V0.74 V (0.15%)386.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.33 V (0.07%)479.7 V0.55 V (0.11%)289.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 30 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 0.33V (0.07%) and delivers 479.7V at the load.

What size aluminum wire is required for 500 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.55V (0.11%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.