⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.22V (0.67%)
Voltage at Load End478.0 VLoss: 1.95 V (1689.6 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A475.26 V (99.01%)4.7 V783.96 V (163.33%)411589.9 WDrop/Amp High
12 AWG3.31 mm²20 A298.65 V (62.22%)181.3 V492.64 V (102.63%)258642.6 WDrop/Amp High
10 AWG5.26 mm²30 A187.94 V (39.15%)292.1 V310.01 V (64.58%)162758.0 WDrop/Amp High
8 AWG8.37 mm²50 A118.11 V (24.61%)361.9 V194.82 V (40.59%)102282.8 WDrop/Amp High
6 AWG13.3 mm²65 A74.33 V (15.48%)405.7 V122.6 V (25.54%)64368.9 WDrop/Amp High
4 AWG21.15 mm²85 A46.74 V (9.74%)433.3 V77.1 V (16.06%)40477.9 WDrop/Amp High
3 AWG26.67 mm²100 A37.07 V (7.72%)442.9 V61.14 V (12.74%)32100.0 WDrop/Amp High
2 AWG33.62 mm²115 A29.4 V (6.13%)450.6 V48.5 V (10.1%)25464.2 WDrop/Amp High
1 AWG42.41 mm²130 A23.31 V (4.86%)456.7 V38.45 V (8.01%)20186.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.48 V (3.85%)461.5 V30.48 V (6.35%)16005.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.66 V (3.05%)465.3 V24.18 V (5.04%)12696.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.63 V (2.42%)468.4 V19.18 V (4.0%)10070.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.22 V (1.92%)470.8 V15.21 V (3.17%)7986.1 WDrop/Amp High
250 kcmil126.7 mm²255 A7.8 V (1.63%)472.2 V12.87 V (2.68%)6757.0 WDrop/Amp High
300 kcmil152.0 mm²285 A6.5 V (1.35%)473.5 V10.73 V (2.23%)5632.3 WDrop/Amp High
350 kcmil177.3 mm²310 A5.58 V (1.16%)474.4 V9.2 V (1.92%)4828.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.88 V (1.02%)475.1 V8.04 V (1.68%)4223.5 WDrop/Amp High
500 kcmil253.4 mm²380 A3.9 V (0.81%)476.1 V6.44 V (1.34%)3378.5 WDrop/Amp High
600 kcmil304.0 mm²420 A3.25 V (0.68%)476.7 V5.36 V (1.12%)2816.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.6 V (0.54%)477.4 V4.29 V (0.89%)2252.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.95 V (0.41%)478.0 V3.22 V (0.67%)1689.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 175 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 1.95V (0.41%) and delivers 478.0V at the load.

What size aluminum wire is required for 500 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.22V (0.67%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.