⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 300 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.37V (2.65%)
Voltage at Load End236.1 VLoss: 3.86 V (1930.9 W)
Power & Breaker (125%)120.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A940.78 V (391.99%)0.0 V1551.84 V (646.6%)470388.5 WDrop/Amp High
12 AWG3.31 mm²20 A591.18 V (246.33%)0.0 V975.18 V (406.32%)295591.5 WDrop/Amp High
10 AWG5.26 mm²30 A372.02 V (155.01%)0.0 V613.66 V (255.69%)186009.1 WDrop/Amp High
8 AWG8.37 mm²50 A233.79 V (97.41%)6.2 V385.64 V (160.68%)116894.6 WDrop/Amp High
6 AWG13.3 mm²65 A147.13 V (61.3%)92.9 V242.69 V (101.12%)73564.5 WDrop/Amp High
4 AWG21.15 mm²85 A92.52 V (38.55%)147.5 V152.62 V (63.59%)46260.4 WDrop/Amp High
3 AWG26.67 mm²100 A73.37 V (30.57%)166.6 V121.03 V (50.43%)36685.7 WDrop/Amp High
2 AWG33.62 mm²115 A58.2 V (24.25%)181.8 V96.01 V (40.0%)29102.0 WDrop/Amp High
1 AWG42.41 mm²130 A46.14 V (19.23%)193.9 V76.11 V (31.71%)23070.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.58 V (15.24%)203.4 V60.34 V (25.14%)18291.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.02 V (12.09%)211.0 V47.87 V (19.95%)14510.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.02 V (9.59%)217.0 V37.97 V (15.82%)11509.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.25 V (7.61%)221.7 V30.11 V (12.55%)9126.9 WDrop/Amp High
250 kcmil126.7 mm²255 A15.44 V (6.44%)224.6 V25.48 V (10.62%)7722.2 WDrop/Amp High
300 kcmil152.0 mm²285 A12.87 V (5.36%)227.1 V21.24 V (8.85%)6436.9 WDrop/Amp High
350 kcmil177.3 mm²310 A11.04 V (4.6%)229.0 V18.21 V (7.59%)5518.4 WDrop/Amp High
400 kcmil202.7 mm²335 A9.65 V (4.02%)230.3 V15.92 V (6.64%)4826.9 WDrop/Amp High
500 kcmil253.4 mm²380 A7.72 V (3.22%)232.3 V12.74 V (5.31%)3861.1 WDrop/Amp High
600 kcmil304.0 mm²420 A6.44 V (2.68%)233.6 V10.62 V (4.42%)3218.4 WDrop/Amp High
750 kcmil380.0 mm²475 A5.15 V (2.15%)234.9 V8.49 V (3.54%)2574.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.86 V (1.61%)236.1 V6.37 V (2.65%)1930.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 300 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.86V (1.61%) and delivers 236.1V at the load.

What size aluminum wire is required for 500 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.37V (2.65%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.