🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.34V (0.97%)
Voltage at Load End239.3 VLoss: 0.71 V (389.4 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A344.95 V (143.73%)0.0 V569.01 V (237.09%)189723.3 WDrop/Amp High
12 AWG3.31 mm²20 A216.77 V (90.32%)23.2 V357.56 V (148.99%)119221.9 WDrop/Amp High
10 AWG5.26 mm²30 A136.41 V (56.84%)103.6 V225.01 V (93.75%)75023.7 WDrop/Amp High
8 AWG8.37 mm²50 A85.72 V (35.72%)154.3 V141.4 V (58.92%)47147.5 WDrop/Amp High
6 AWG13.3 mm²65 A53.95 V (22.48%)186.1 V88.99 V (37.08%)29671.0 WDrop/Amp High
4 AWG21.15 mm²85 A33.92 V (14.14%)206.1 V55.96 V (23.32%)18658.4 WDrop/Amp High
3 AWG26.67 mm²100 A26.9 V (11.21%)213.1 V44.38 V (18.49%)14796.6 WDrop/Amp High
2 AWG33.62 mm²115 A21.34 V (8.89%)218.7 V35.2 V (14.67%)11737.8 WDrop/Amp High
1 AWG42.41 mm²130 A16.92 V (7.05%)223.1 V27.91 V (11.63%)9305.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.41 V (5.59%)226.6 V22.13 V (9.22%)7377.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.64 V (4.43%)229.4 V17.55 V (7.31%)5852.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.44 V (3.52%)231.6 V13.92 V (5.8%)4642.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.69 V (2.79%)233.3 V11.04 V (4.6%)3681.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.66 V (2.36%)234.3 V9.34 V (3.89%)3114.6 WDrop/Amp High
300 kcmil152.0 mm²285 A4.72 V (1.97%)235.3 V7.79 V (3.24%)2596.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.05 V (1.69%)236.0 V6.68 V (2.78%)2225.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.54 V (1.47%)236.5 V5.84 V (2.43%)1946.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.83 V (1.18%)237.2 V4.67 V (1.95%)1557.3 WDrop/Amp High
600 kcmil304.0 mm²420 A2.36 V (0.98%)237.6 V3.89 V (1.62%)1298.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.89 V (0.79%)238.1 V3.11 V (1.3%)1038.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.42 V (0.59%)238.6 V2.34 V (0.97%)778.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 100 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.71V (0.29%) and delivers 239.3V at the load.

What size aluminum wire is required for 550 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.34V (0.97%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.