🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 50 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.17V (0.49%)
Voltage at Load End239.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A172.48 V (71.86%)67.5 V284.5 V (118.54%)94861.7 WDrop/Amp High
12 AWG3.31 mm²20 A108.38 V (45.16%)131.6 V178.78 V (74.49%)59611.0 WDrop/Amp High
10 AWG5.26 mm²30 A68.2 V (28.42%)171.8 V112.5 V (46.88%)37511.8 WDrop/Amp High
8 AWG8.37 mm²50 A42.86 V (17.86%)197.1 V70.7 V (29.46%)23573.7 WDrop/Amp High
6 AWG13.3 mm²65 A26.97 V (11.24%)213.0 V44.49 V (18.54%)14835.5 WDrop/Amp High
4 AWG21.15 mm²85 A16.96 V (7.07%)223.0 V27.98 V (11.66%)9329.2 WDrop/Amp High
3 AWG26.67 mm²100 A13.45 V (5.6%)226.5 V22.19 V (9.25%)7398.3 WDrop/Amp High
2 AWG33.62 mm²115 A10.67 V (4.45%)229.3 V17.6 V (7.33%)5868.9 WDrop/Amp High
1 AWG42.41 mm²130 A8.46 V (3.52%)231.5 V13.95 V (5.81%)4652.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.71 V (2.79%)233.3 V11.06 V (4.61%)3688.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.32 V (2.22%)234.7 V8.78 V (3.66%)2926.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.22 V (1.76%)235.8 V6.96 V (2.9%)2321.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.35 V (1.39%)236.7 V5.52 V (2.3%)1840.6 WDrop/Amp High
250 kcmil126.7 mm²255 A2.83 V (1.18%)237.2 V4.67 V (1.95%)1557.3 WDrop/Amp High
300 kcmil152.0 mm²285 A2.36 V (0.98%)237.6 V3.89 V (1.62%)1298.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.02 V (0.84%)238.0 V3.34 V (1.39%)1112.9 WDrop/Amp High
400 kcmil202.7 mm²335 A1.77 V (0.74%)238.2 V2.92 V (1.22%)973.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.42 V (0.59%)238.6 V2.34 V (0.97%)778.7 WDrop/Amp High
600 kcmil304.0 mm²420 A1.18 V (0.49%)238.8 V1.95 V (0.81%)649.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.94 V (0.39%)239.1 V1.56 V (0.65%)519.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.71 V (0.3%)239.3 V1.17 V (0.49%)389.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 50 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (0.15%) and delivers 239.7V at the load.

What size aluminum wire is required for 550 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.17V (0.49%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.