550 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.23%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.87V (0.78%)
Voltage at Load End239.4 VLoss: 0.56 V (311.6 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A275.96 V (114.98%)0.0 V455.21 V (189.67%)151778.7 WDrop/Amp High
12 AWG3.31 mm²20 A173.41 V (72.26%)66.6 V286.05 V (119.19%)95377.5 WDrop/Amp High
10 AWG5.26 mm²30 A109.13 V (45.47%)130.9 V180.01 V (75.0%)60018.9 WDrop/Amp High
8 AWG8.37 mm²50 A68.58 V (28.57%)171.4 V113.12 V (47.13%)37718.0 WDrop/Amp High
6 AWG13.3 mm²65 A43.16 V (17.98%)196.8 V71.19 V (29.66%)23736.8 WDrop/Amp High
4 AWG21.15 mm²85 A27.14 V (11.31%)212.9 V44.77 V (18.65%)14926.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.52 V (8.97%)218.5 V35.5 V (14.79%)11837.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.07 V (7.11%)222.9 V28.16 V (11.73%)9390.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.53 V (5.64%)226.5 V22.33 V (9.3%)7444.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.73 V (4.47%)229.3 V17.7 V (7.38%)5902.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.51 V (3.55%)231.5 V14.04 V (5.85%)4681.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.75 V (2.81%)233.2 V11.14 V (4.64%)3713.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.35 V (2.23%)234.6 V8.83 V (3.68%)2945.0 WDrop/Amp High
250 kcmil126.7 mm²255 A4.53 V (1.89%)235.5 V7.47 V (3.11%)2491.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.78 V (1.57%)236.2 V6.23 V (2.6%)2077.0 WDrop/Amp High
350 kcmil177.3 mm²310 A3.24 V (1.35%)236.8 V5.34 V (2.23%)1780.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.83 V (1.18%)237.2 V4.67 V (1.95%)1557.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (0.94%)237.7 V3.74 V (1.56%)1245.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.89 V (0.79%)238.1 V3.11 V (1.3%)1038.5 WDrop/Amp High
750 kcmil380.0 mm²475 A1.51 V (0.63%)238.5 V2.49 V (1.04%)830.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.13 V (0.47%)238.9 V1.87 V (0.78%)623.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 80 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.56V (0.23%) and delivers 239.4V at the load.

What size aluminum wire is required for 550 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.87V (0.78%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.