🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.92V (1.22%)
Voltage at Load End239.1 VLoss: 0.89 V (486.8 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A431.19 V (179.66%)0.0 V711.26 V (296.36%)237154.2 WDrop/Amp High
12 AWG3.31 mm²20 A270.96 V (112.9%)0.0 V446.96 V (186.23%)149027.4 WDrop/Amp High
10 AWG5.26 mm²30 A170.51 V (71.05%)69.5 V281.26 V (117.19%)93779.6 WDrop/Amp High
8 AWG8.37 mm²50 A107.15 V (44.65%)132.8 V176.75 V (73.65%)58934.4 WDrop/Amp High
6 AWG13.3 mm²65 A67.43 V (28.1%)172.6 V111.23 V (46.35%)37088.8 WDrop/Amp High
4 AWG21.15 mm²85 A42.41 V (17.67%)197.6 V69.95 V (29.15%)23323.0 WDrop/Amp High
3 AWG26.67 mm²100 A33.63 V (14.01%)206.4 V55.47 V (23.11%)18495.7 WDrop/Amp High
2 AWG33.62 mm²115 A26.68 V (11.12%)213.3 V44.0 V (18.34%)14672.2 WDrop/Amp High
1 AWG42.41 mm²130 A21.15 V (8.81%)218.9 V34.88 V (14.53%)11631.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.77 V (6.99%)223.2 V27.66 V (11.52%)9221.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.3 V (5.54%)226.7 V21.94 V (9.14%)7315.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.55 V (4.4%)229.4 V17.4 V (7.25%)5802.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.37 V (3.49%)231.6 V13.8 V (5.75%)4601.5 WDrop/Amp High
250 kcmil126.7 mm²255 A7.08 V (2.95%)232.9 V11.68 V (4.87%)3893.3 WDrop/Amp High
300 kcmil152.0 mm²285 A5.9 V (2.46%)234.1 V9.73 V (4.06%)3245.3 WDrop/Amp High
350 kcmil177.3 mm²310 A5.06 V (2.11%)234.9 V8.34 V (3.48%)2782.2 WDrop/Amp High
400 kcmil202.7 mm²335 A4.42 V (1.84%)235.6 V7.3 V (3.04%)2433.6 WDrop/Amp High
500 kcmil253.4 mm²380 A3.54 V (1.47%)236.5 V5.84 V (2.43%)1946.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.95 V (1.23%)237.0 V4.87 V (2.03%)1622.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.36 V (0.98%)237.6 V3.89 V (1.62%)1298.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.77 V (0.74%)238.2 V2.92 V (1.22%)973.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 125 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.89V (0.37%) and delivers 239.1V at the load.

What size aluminum wire is required for 550 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.92V (1.22%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.