550 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.47V (0.39%)
Voltage at Load End119.9 VLoss: 0.14 V (77.9 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A68.99 V (57.49%)51.0 V113.8 V (94.83%)37944.7 WDrop/Amp High
12 AWG3.31 mm²20 A43.35 V (36.13%)76.6 V71.51 V (59.59%)23844.4 WDrop/Amp High
10 AWG5.26 mm²30 A27.28 V (22.73%)92.7 V45.0 V (37.5%)15004.7 WDrop/Amp High
8 AWG8.37 mm²50 A17.14 V (14.29%)102.9 V28.28 V (23.57%)9429.5 WDrop/Amp High
6 AWG13.3 mm²65 A10.79 V (8.99%)109.2 V17.8 V (14.83%)5934.2 WDrop/Amp High
4 AWG21.15 mm²85 A6.78 V (5.65%)113.2 V11.19 V (9.33%)3731.7 WDrop/Amp High
3 AWG26.67 mm²100 A5.38 V (4.48%)114.6 V8.88 V (7.4%)2959.3 WDrop/Amp High
2 AWG33.62 mm²115 A4.27 V (3.56%)115.7 V7.04 V (5.87%)2347.6 WDrop/Amp High
1 AWG42.41 mm²130 A3.38 V (2.82%)116.6 V5.58 V (4.65%)1861.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.68 V (2.24%)117.3 V4.43 V (3.69%)1475.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.13 V (1.77%)117.9 V3.51 V (2.93%)1170.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.69 V (1.41%)118.3 V2.78 V (2.32%)928.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.34 V (1.12%)118.7 V2.21 V (1.84%)736.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.13 V (0.94%)118.9 V1.87 V (1.56%)622.9 WDrop/Amp High
300 kcmil152.0 mm²285 A0.94 V (0.79%)119.1 V1.56 V (1.3%)519.2 WDrop/Amp High
350 kcmil177.3 mm²310 A0.81 V (0.67%)119.2 V1.34 V (1.11%)445.1 WDrop/Amp High
400 kcmil202.7 mm²335 A0.71 V (0.59%)119.3 V1.17 V (0.97%)389.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.57 V (0.47%)119.4 V0.93 V (0.78%)311.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.47 V (0.39%)119.5 V0.78 V (0.65%)259.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.38 V (0.31%)119.6 V0.62 V (0.52%)207.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.28 V (0.24%)119.7 V0.47 V (0.39%)155.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 20 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.14V (0.12%) and delivers 119.9V at the load.

What size aluminum wire is required for 550 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.47V (0.39%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.