⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.23%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.93V (0.78%)
Voltage at Load End119.7 VLoss: 0.28 V (155.8 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A137.98 V (114.98%)0.0 V227.6 V (189.67%)75889.3 WDrop/Amp High
12 AWG3.31 mm²20 A86.71 V (72.26%)33.3 V143.03 V (119.19%)47688.8 WDrop/Amp High
10 AWG5.26 mm²30 A54.56 V (45.47%)65.4 V90.0 V (75.0%)30009.5 WDrop/Amp High
8 AWG8.37 mm²50 A34.29 V (28.57%)85.7 V56.56 V (47.13%)18859.0 WDrop/Amp High
6 AWG13.3 mm²65 A21.58 V (17.98%)98.4 V35.6 V (29.66%)11868.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.57 V (11.31%)106.4 V22.38 V (18.65%)7463.3 WDrop/Amp High
3 AWG26.67 mm²100 A10.76 V (8.97%)109.2 V17.75 V (14.79%)5918.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.54 V (7.11%)111.5 V14.08 V (11.73%)4695.1 WDrop/Amp High
1 AWG42.41 mm²130 A6.77 V (5.64%)113.2 V11.16 V (9.3%)3722.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.37 V (4.47%)114.6 V8.85 V (7.38%)2951.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.26 V (3.55%)115.7 V7.02 V (5.85%)2340.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.38 V (2.81%)116.6 V5.57 V (4.64%)1856.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.68 V (2.23%)117.3 V4.42 V (3.68%)1472.5 WDrop/Amp High
250 kcmil126.7 mm²255 A2.27 V (1.89%)117.7 V3.74 V (3.11%)1245.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.89 V (1.57%)118.1 V3.11 V (2.6%)1038.5 WDrop/Amp High
350 kcmil177.3 mm²310 A1.62 V (1.35%)118.4 V2.67 V (2.23%)890.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.42 V (1.18%)118.6 V2.34 V (1.95%)778.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.13 V (0.94%)118.9 V1.87 V (1.56%)622.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.94 V (0.79%)119.1 V1.56 V (1.3%)519.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.76 V (0.63%)119.2 V1.25 V (1.04%)415.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.57 V (0.47%)119.4 V0.93 V (0.78%)311.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 40 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.28V (0.23%) and delivers 119.7V at the load.

What size aluminum wire is required for 550 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.93V (0.78%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.