🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.47%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.87V (1.56%)
Voltage at Load End119.4 VLoss: 0.56 V (311.6 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A275.96 V (229.97%)0.0 V455.21 V (379.34%)151778.7 WDrop/Amp High
12 AWG3.31 mm²20 A173.41 V (144.51%)0.0 V286.05 V (238.38%)95377.5 WDrop/Amp High
10 AWG5.26 mm²30 A109.13 V (90.94%)10.9 V180.01 V (150.0%)60018.9 WDrop/Amp High
8 AWG8.37 mm²50 A68.58 V (57.15%)51.4 V113.12 V (94.27%)37718.0 WDrop/Amp High
6 AWG13.3 mm²65 A43.16 V (35.96%)76.8 V71.19 V (59.33%)23736.8 WDrop/Amp High
4 AWG21.15 mm²85 A27.14 V (22.62%)92.9 V44.77 V (37.31%)14926.7 WDrop/Amp High
3 AWG26.67 mm²100 A21.52 V (17.94%)98.5 V35.5 V (29.58%)11837.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.07 V (14.23%)102.9 V28.16 V (23.47%)9390.2 WDrop/Amp High
1 AWG42.41 mm²130 A13.53 V (11.28%)106.5 V22.33 V (18.6%)7444.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.73 V (8.94%)109.3 V17.7 V (14.75%)5902.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.51 V (7.09%)111.5 V14.04 V (11.7%)4681.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.75 V (5.63%)113.2 V11.14 V (9.28%)3713.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.35 V (4.46%)114.6 V8.83 V (7.36%)2945.0 WDrop/Amp High
250 kcmil126.7 mm²255 A4.53 V (3.78%)115.5 V7.47 V (6.23%)2491.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.78 V (3.15%)116.2 V6.23 V (5.19%)2077.0 WDrop/Amp High
350 kcmil177.3 mm²310 A3.24 V (2.7%)116.8 V5.34 V (4.45%)1780.6 WDrop/Amp High
400 kcmil202.7 mm²335 A2.83 V (2.36%)117.2 V4.67 V (3.89%)1557.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (1.89%)117.7 V3.74 V (3.11%)1245.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.89 V (1.57%)118.1 V3.11 V (2.6%)1038.5 WDrop/Amp High
750 kcmil380.0 mm²475 A1.51 V (1.26%)118.5 V2.49 V (2.08%)830.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.13 V (0.94%)118.9 V1.87 V (1.56%)623.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 80 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.56V (0.47%) and delivers 119.4V at the load.

What size aluminum wire is required for 550 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.87V (1.56%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.