550 Amp Wire Size at 200 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.67V (38.93%)
Voltage at Load End11.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 200 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A689.9 V (5749.19%)0.0 V1138.02 V (9483.48%)379446.7 WDrop/Amp High
12 AWG3.31 mm²20 A433.53 V (3612.79%)0.0 V715.13 V (5959.41%)238443.8 WDrop/Amp High
10 AWG5.26 mm²30 A272.81 V (2273.44%)0.0 V450.01 V (3750.12%)150047.4 WDrop/Amp High
8 AWG8.37 mm²50 A171.45 V (1428.71%)0.0 V282.8 V (2356.71%)94295.0 WDrop/Amp High
6 AWG13.3 mm²65 A107.89 V (899.12%)0.0 V177.98 V (1483.13%)59342.0 WDrop/Amp High
4 AWG21.15 mm²85 A67.85 V (565.41%)0.0 V111.92 V (932.65%)37316.7 WDrop/Amp High
3 AWG26.67 mm²100 A53.81 V (448.38%)0.0 V88.75 V (739.62%)29593.1 WDrop/Amp High
2 AWG33.62 mm²115 A42.68 V (355.69%)0.0 V70.41 V (586.72%)23475.6 WDrop/Amp High
1 AWG42.41 mm²130 A33.84 V (281.97%)0.0 V55.81 V (465.12%)18610.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.83 V (223.56%)0.0 V44.25 V (368.77%)14755.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.28 V (177.34%)0.0 V35.1 V (292.54%)11704.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.88 V (140.67%)0.0 V27.84 V (232.04%)9284.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.39 V (111.55%)0.0 V22.08 V (184.01%)7362.4 WDrop/Amp High
250 kcmil126.7 mm²255 A11.33 V (94.38%)0.7 V18.68 V (155.69%)6229.3 WDrop/Amp High
300 kcmil152.0 mm²285 A9.44 V (78.67%)2.6 V15.57 V (129.77%)5192.4 WDrop/Amp High
350 kcmil177.3 mm²310 A8.09 V (67.45%)3.9 V13.35 V (111.26%)4451.5 WDrop/Amp High
400 kcmil202.7 mm²335 A7.08 V (59.0%)4.9 V11.68 V (97.31%)3893.7 WDrop/Amp High
500 kcmil253.4 mm²380 A5.66 V (47.19%)6.3 V9.34 V (77.84%)3114.6 WDrop/Amp High
600 kcmil304.0 mm²420 A4.72 V (39.34%)7.3 V7.79 V (64.89%)2596.2 WDrop/Amp High
750 kcmil380.0 mm²475 A3.78 V (31.47%)8.2 V6.23 V (51.91%)2077.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.83 V (23.6%)9.2 V4.67 V (38.93%)1557.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 200 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 200 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.67V (38.93%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.