🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 0.98%
Aluminum Wire (≤3% Drop)4 AWGDrop: 2.44V (1.02%)
Voltage at Load End237.6 VLoss: 2.35 V (141.2 W)
Power & Breaker (125%)14.4 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A15.05 V (6.27%)224.9 V24.83 V (10.35%)903.1 WDrop/Amp High
12 AWG3.31 mm²20 A9.46 V (3.94%)230.5 V15.6 V (6.5%)567.5 WDrop/Amp High
10 AWG5.26 mm²30 A5.95 V (2.48%)234.0 V9.82 V (4.09%)357.1 WDrop/Amp High
8 AWG8.37 mm²50 A3.74 V (1.56%)236.3 V6.17 V (2.57%)224.4 WDrop/Amp High
6 AWG13.3 mm²65 A2.35 V (0.98%)237.6 V3.88 V (1.62%)141.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.48 V (0.62%)238.5 V2.44 V (1.02%)88.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.17 V (0.49%)238.8 V1.94 V (0.81%)70.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.93 V (0.39%)239.1 V1.54 V (0.64%)55.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.74 V (0.31%)239.3 V1.22 V (0.51%)44.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.59 V (0.24%)239.4 V0.97 V (0.4%)35.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.46 V (0.19%)239.5 V0.77 V (0.32%)27.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.37 V (0.15%)239.6 V0.61 V (0.25%)22.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.29 V (0.12%)239.7 V0.48 V (0.2%)17.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.25 V (0.1%)239.8 V0.41 V (0.17%)14.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.21 V (0.09%)239.8 V0.34 V (0.14%)12.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.07%)239.8 V0.29 V (0.12%)10.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.15 V (0.06%)239.8 V0.25 V (0.11%)9.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.05%)239.9 V0.2 V (0.08%)7.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.04%)239.9 V0.17 V (0.07%)6.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.03%)239.9 V0.14 V (0.06%)4.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.03%)239.9 V0.1 V (0.04%)3.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 40 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 2.35V (0.98%) and delivers 237.6V at the load.

What size aluminum wire is required for 60 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 2.44V (1.02%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.