🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 50 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 1.23%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.05V (1.27%)
Voltage at Load End237.1 VLoss: 2.94 V (176.6 W)
Power & Breaker (125%)14.4 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A18.82 V (7.84%)221.2 V31.04 V (12.93%)1128.9 WDrop/Amp High
12 AWG3.31 mm²20 A11.82 V (4.93%)228.2 V19.5 V (8.13%)709.4 WDrop/Amp High
10 AWG5.26 mm²30 A7.44 V (3.1%)232.6 V12.27 V (5.11%)446.4 WDrop/Amp High
8 AWG8.37 mm²50 A4.68 V (1.95%)235.3 V7.71 V (3.21%)280.5 WDrop/Amp High
6 AWG13.3 mm²65 A2.94 V (1.23%)237.1 V4.85 V (2.02%)176.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.85 V (0.77%)238.1 V3.05 V (1.27%)111.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.47 V (0.61%)238.5 V2.42 V (1.01%)88.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.16 V (0.49%)238.8 V1.92 V (0.8%)69.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.92 V (0.38%)239.1 V1.52 V (0.63%)55.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.73 V (0.3%)239.3 V1.21 V (0.5%)43.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.58 V (0.24%)239.4 V0.96 V (0.4%)34.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.46 V (0.19%)239.5 V0.76 V (0.32%)27.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.37 V (0.15%)239.6 V0.6 V (0.25%)21.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.31 V (0.13%)239.7 V0.51 V (0.21%)18.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.26 V (0.11%)239.7 V0.42 V (0.18%)15.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.22 V (0.09%)239.8 V0.36 V (0.15%)13.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.19 V (0.08%)239.8 V0.32 V (0.13%)11.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.15 V (0.06%)239.8 V0.25 V (0.11%)9.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.05%)239.9 V0.21 V (0.09%)7.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.17 V (0.07%)6.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.13 V (0.05%)4.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 50 feet one-way at 240V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 2.94V (1.23%) and delivers 237.1V at the load.

What size aluminum wire is required for 60 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.05V (1.27%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.