⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.56%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.86V (1.86%)
Voltage at Load End206.8 VLoss: 1.17 V (1216.5 W)
Power & Breaker (125%)216.16 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A570.32 V (274.19%)0.0 V940.75 V (452.29%)592689.5 WDrop/Amp High
12 AWG3.31 mm²20 A358.39 V (172.3%)0.0 V591.17 V (284.22%)372445.3 WDrop/Amp High
10 AWG5.26 mm²30 A225.52 V (108.43%)0.0 V372.01 V (178.85%)234371.5 WDrop/Amp High
8 AWG8.37 mm²50 A141.73 V (68.14%)66.3 V233.78 V (112.4%)147287.2 WDrop/Amp High
6 AWG13.3 mm²65 A89.19 V (42.88%)118.8 V147.13 V (70.73%)92691.3 WDrop/Amp High
4 AWG21.15 mm²85 A56.09 V (26.97%)151.9 V92.52 V (44.48%)58288.1 WDrop/Amp High
3 AWG26.67 mm²100 A44.48 V (21.38%)163.5 V73.37 V (35.27%)46224.0 WDrop/Amp High
2 AWG33.62 mm²115 A35.28 V (16.96%)172.7 V58.2 V (27.98%)36668.5 WDrop/Amp High
1 AWG42.41 mm²130 A27.97 V (13.45%)180.0 V46.14 V (22.18%)29068.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.18 V (10.66%)185.8 V36.58 V (17.59%)23047.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.59 V (8.46%)190.4 V29.02 V (13.95%)18282.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.95 V (6.71%)194.0 V23.02 V (11.07%)14501.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.07 V (5.32%)196.9 V18.25 V (8.78%)11499.9 WDrop/Amp High
250 kcmil126.7 mm²255 A9.36 V (4.5%)198.6 V15.44 V (7.43%)9730.0 WDrop/Amp High
300 kcmil152.0 mm²285 A7.8 V (3.75%)200.2 V12.87 V (6.19%)8110.5 WDrop/Amp High
350 kcmil177.3 mm²310 A6.69 V (3.22%)201.3 V11.04 V (5.31%)6953.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.85 V (2.81%)202.1 V9.65 V (4.64%)6081.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.68 V (2.25%)203.3 V7.72 V (3.71%)4865.0 WDrop/Amp High
600 kcmil304.0 mm²420 A3.9 V (1.88%)204.1 V6.44 V (3.09%)4055.2 WDrop/Amp High
750 kcmil380.0 mm²475 A3.12 V (1.5%)204.9 V5.15 V (2.48%)3244.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.34 V (1.13%)205.7 V3.86 V (1.86%)2433.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 175 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.17V (0.56%) and delivers 206.8V at the load.

What size aluminum wire is required for 600 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.86V (1.86%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.