🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.77V (2.82%)
Voltage at Load End233.5 VLoss: 6.53 V (791.3 W)
Power & Breaker (125%)29.1 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A133.07 V (55.45%)106.9 V219.51 V (91.46%)16134.3 WDrop/Amp High
12 AWG3.31 mm²20 A83.62 V (34.84%)156.4 V137.94 V (57.47%)10138.8 WDrop/Amp High
10 AWG5.26 mm²30 A52.62 V (21.93%)187.4 V86.8 V (36.17%)6380.1 WDrop/Amp High
8 AWG8.37 mm²50 A33.07 V (13.78%)206.9 V54.55 V (22.73%)4009.5 WDrop/Amp High
6 AWG13.3 mm²65 A20.81 V (8.67%)219.2 V34.33 V (14.3%)2523.3 WDrop/Amp High
4 AWG21.15 mm²85 A13.09 V (5.45%)226.9 V21.59 V (8.99%)1586.7 WDrop/Amp High
3 AWG26.67 mm²100 A10.38 V (4.32%)229.6 V17.12 V (7.13%)1258.3 W~ ≤5%
2 AWG33.62 mm²115 A8.23 V (3.43%)231.8 V13.58 V (5.66%)998.2 W~ ≤5%
1 AWG42.41 mm²130 A6.53 V (2.72%)233.5 V10.77 V (4.49%)791.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.17 V (2.16%)234.8 V8.54 V (3.56%)627.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.1 V (1.71%)235.9 V6.77 V (2.82%)497.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.26 V (1.36%)236.7 V5.37 V (2.24%)394.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.58 V (1.08%)237.4 V4.26 V (1.77%)313.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.18 V (0.91%)237.8 V3.6 V (1.5%)264.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.82 V (0.76%)238.2 V3.0 V (1.25%)220.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.56 V (0.65%)238.4 V2.58 V (1.07%)189.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.37 V (0.57%)238.6 V2.25 V (0.94%)165.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.09 V (0.46%)238.9 V1.8 V (0.75%)132.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.91 V (0.38%)239.1 V1.5 V (0.63%)110.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.73 V (0.3%)239.3 V1.2 V (0.5%)88.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.55 V (0.23%)239.5 V0.9 V (0.38%)66.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 350 feet one-way at 240V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 6.53V (2.72%) and delivers 233.5V at the load.

What size aluminum wire is required for 70 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.77V (2.82%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.