⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 150 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.86V (0.8%)
Voltage at Load End478.8 VLoss: 1.17 V (1419.2 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 150 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A570.32 V (118.82%)0.0 V940.75 V (195.99%)691471.0 WDrop/Amp High
12 AWG3.31 mm²20 A358.39 V (74.66%)121.6 V591.17 V (123.16%)434519.6 WDrop/Amp High
10 AWG5.26 mm²30 A225.52 V (46.98%)254.5 V372.01 V (77.5%)273433.4 WDrop/Amp High
8 AWG8.37 mm²50 A141.73 V (29.53%)338.3 V233.78 V (48.7%)171835.1 WDrop/Amp High
6 AWG13.3 mm²65 A89.19 V (18.58%)390.8 V147.13 V (30.65%)108139.8 WDrop/Amp High
4 AWG21.15 mm²85 A56.09 V (11.68%)423.9 V92.52 V (19.27%)68002.8 WDrop/Amp High
3 AWG26.67 mm²100 A44.48 V (9.27%)435.5 V73.37 V (15.29%)53928.0 WDrop/Amp High
2 AWG33.62 mm²115 A35.28 V (7.35%)444.7 V58.2 V (12.13%)42779.9 WDrop/Amp High
1 AWG42.41 mm²130 A27.97 V (5.83%)452.0 V46.14 V (9.61%)33913.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.18 V (4.62%)457.8 V36.58 V (7.62%)26888.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.59 V (3.67%)462.4 V29.02 V (6.05%)21329.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.95 V (2.91%)466.0 V23.02 V (4.8%)16918.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.07 V (2.31%)468.9 V18.25 V (3.8%)13416.6 WDrop/Amp High
250 kcmil126.7 mm²255 A9.36 V (1.95%)470.6 V15.44 V (3.22%)11351.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.8 V (1.63%)472.2 V12.87 V (2.68%)9462.2 WDrop/Amp High
350 kcmil177.3 mm²310 A6.69 V (1.39%)473.3 V11.04 V (2.3%)8112.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.85 V (1.22%)474.1 V9.65 V (2.01%)7095.5 WDrop/Amp High
500 kcmil253.4 mm²380 A4.68 V (0.98%)475.3 V7.72 V (1.61%)5675.8 WDrop/Amp High
600 kcmil304.0 mm²420 A3.9 V (0.81%)476.1 V6.44 V (1.34%)4731.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.12 V (0.65%)476.9 V5.15 V (1.07%)3784.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.34 V (0.49%)477.7 V3.86 V (0.8%)2838.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 150 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 150 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.17V (0.24%) and delivers 478.8V at the load.

What size aluminum wire is required for 700 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.86V (0.8%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.