⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.1%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.54V (0.32%)
Voltage at Load End479.5 VLoss: 0.47 V (567.7 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A228.13 V (47.53%)251.9 V376.3 V (78.4%)276588.4 WDrop/Amp High
12 AWG3.31 mm²20 A143.35 V (29.87%)336.6 V236.47 V (49.26%)173807.8 WDrop/Amp High
10 AWG5.26 mm²30 A90.21 V (18.79%)389.8 V148.8 V (31.0%)109373.4 WDrop/Amp High
8 AWG8.37 mm²50 A56.69 V (11.81%)423.3 V93.51 V (19.48%)68734.0 WDrop/Amp High
6 AWG13.3 mm²65 A35.68 V (7.43%)444.3 V58.85 V (12.26%)43255.9 WDrop/Amp High
4 AWG21.15 mm²85 A22.44 V (4.67%)457.6 V37.01 V (7.71%)27201.1 WDrop/Amp High
3 AWG26.67 mm²100 A17.79 V (3.71%)462.2 V29.35 V (6.11%)21571.2 WDrop/Amp High
2 AWG33.62 mm²115 A14.11 V (2.94%)465.9 V23.28 V (4.85%)17112.0 WDrop/Amp High
1 AWG42.41 mm²130 A11.19 V (2.33%)468.8 V18.46 V (3.84%)13565.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.87 V (1.85%)471.1 V14.63 V (3.05%)10755.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.04 V (1.47%)473.0 V11.61 V (2.42%)8531.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.58 V (1.16%)474.4 V9.21 V (1.92%)6767.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.43 V (0.92%)475.6 V7.3 V (1.52%)5366.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.75 V (0.78%)476.3 V6.18 V (1.29%)4540.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.12 V (0.65%)476.9 V5.15 V (1.07%)3784.9 WDrop/Amp High
350 kcmil177.3 mm²310 A2.68 V (0.56%)477.3 V4.41 V (0.92%)3244.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.34 V (0.49%)477.7 V3.86 V (0.8%)2838.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.87 V (0.39%)478.1 V3.09 V (0.64%)2270.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.56 V (0.33%)478.4 V2.57 V (0.54%)1892.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.25 V (0.26%)478.8 V2.06 V (0.43%)1514.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.94 V (0.2%)479.1 V1.54 V (0.32%)1135.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 60 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.47V (0.1%) and delivers 479.5V at the load.

What size aluminum wire is required for 700 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.54V (0.32%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.