⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.2%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.09V (0.64%)
Voltage at Load End479.1 VLoss: 0.94 V (1135.4 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A456.25 V (95.05%)23.7 V752.6 V (156.79%)553176.8 WDrop/Amp High
12 AWG3.31 mm²20 A286.71 V (59.73%)193.3 V472.94 V (98.53%)347615.7 WDrop/Amp High
10 AWG5.26 mm²30 A180.42 V (37.59%)299.6 V297.61 V (62.0%)218746.7 WDrop/Amp High
8 AWG8.37 mm²50 A113.38 V (23.62%)366.6 V187.03 V (38.96%)137468.1 WDrop/Amp High
6 AWG13.3 mm²65 A71.35 V (14.87%)408.6 V117.7 V (24.52%)86511.9 WDrop/Amp High
4 AWG21.15 mm²85 A44.87 V (9.35%)435.1 V74.01 V (15.42%)54402.3 WDrop/Amp High
3 AWG26.67 mm²100 A35.58 V (7.41%)444.4 V58.7 V (12.23%)43142.4 WDrop/Amp High
2 AWG33.62 mm²115 A28.23 V (5.88%)451.8 V46.56 V (9.7%)34223.9 WDrop/Amp High
1 AWG42.41 mm²130 A22.38 V (4.66%)457.6 V36.91 V (7.69%)27130.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.74 V (3.7%)462.3 V29.27 V (6.1%)21510.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.07 V (2.93%)465.9 V23.22 V (4.84%)17063.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.16 V (2.33%)468.8 V18.41 V (3.84%)13535.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.85 V (1.84%)471.1 V14.6 V (3.04%)10733.3 WDrop/Amp High
250 kcmil126.7 mm²255 A7.49 V (1.56%)472.5 V12.36 V (2.57%)9081.4 WDrop/Amp High
300 kcmil152.0 mm²285 A6.24 V (1.3%)473.8 V10.3 V (2.15%)7569.8 WDrop/Amp High
350 kcmil177.3 mm²310 A5.35 V (1.12%)474.6 V8.83 V (1.84%)6489.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.68 V (0.98%)475.3 V7.72 V (1.61%)5676.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.75 V (0.78%)476.3 V6.18 V (1.29%)4540.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.12 V (0.65%)476.9 V5.15 V (1.07%)3784.9 WDrop/Amp High
750 kcmil380.0 mm²475 A2.5 V (0.52%)477.5 V4.12 V (0.86%)3027.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.87 V (0.39%)478.1 V3.09 V (0.64%)2270.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 120 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.94V (0.2%) and delivers 479.1V at the load.

What size aluminum wire is required for 700 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.09V (0.64%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.