🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.51V (0.94%)
Voltage at Load End478.6 VLoss: 1.36 V (1655.8 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A665.37 V (138.62%)0.0 V1097.55 V (228.66%)806716.2 WDrop/Amp High
12 AWG3.31 mm²20 A418.12 V (87.11%)61.9 V689.7 V (143.69%)506939.5 WDrop/Amp High
10 AWG5.26 mm²30 A263.11 V (54.81%)216.9 V434.01 V (90.42%)319005.7 WDrop/Amp High
8 AWG8.37 mm²50 A165.35 V (34.45%)314.7 V272.75 V (56.82%)200474.3 WDrop/Amp High
6 AWG13.3 mm²65 A104.06 V (21.68%)375.9 V171.65 V (35.76%)126163.1 WDrop/Amp High
4 AWG21.15 mm²85 A65.44 V (13.63%)414.6 V107.94 V (22.49%)79336.6 WDrop/Amp High
3 AWG26.67 mm²100 A51.89 V (10.81%)428.1 V85.6 V (17.83%)62916.0 WDrop/Amp High
2 AWG33.62 mm²115 A41.16 V (8.58%)438.8 V67.9 V (14.15%)49909.9 WDrop/Amp High
1 AWG42.41 mm²130 A32.63 V (6.8%)447.4 V53.83 V (11.21%)39565.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.87 V (5.39%)454.1 V42.68 V (8.89%)31369.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.52 V (4.28%)459.5 V33.86 V (7.05%)24884.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.28 V (3.39%)463.7 V26.85 V (5.59%)19738.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.91 V (2.69%)467.1 V21.3 V (4.44%)15652.7 WDrop/Amp High
250 kcmil126.7 mm²255 A10.92 V (2.28%)469.1 V18.02 V (3.75%)13243.6 WDrop/Amp High
300 kcmil152.0 mm²285 A9.11 V (1.9%)470.9 V15.02 V (3.13%)11039.3 WDrop/Amp High
350 kcmil177.3 mm²310 A7.81 V (1.63%)472.2 V12.88 V (2.68%)9464.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.83 V (1.42%)473.2 V11.26 V (2.35%)8278.1 WDrop/Amp High
500 kcmil253.4 mm²380 A5.46 V (1.14%)474.5 V9.01 V (1.88%)6621.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.55 V (0.95%)475.4 V7.51 V (1.56%)5519.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.64 V (0.76%)476.4 V6.01 V (1.25%)4415.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.73 V (0.57%)477.3 V4.51 V (0.94%)3311.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 175 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.36V (0.28%) and delivers 478.6V at the load.

What size aluminum wire is required for 700 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.51V (0.94%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.