⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.21V (1.29%)
Voltage at Load End478.1 VLoss: 1.88 V (2443.8 W)
Power & Breaker (125%)623.54 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A916.58 V (190.95%)0.0 V1511.93 V (314.98%)1190670.8 WDrop/Amp High
12 AWG3.31 mm²20 A575.98 V (120.0%)0.0 V950.09 V (197.94%)748216.1 WDrop/Amp High
10 AWG5.26 mm²30 A362.45 V (75.51%)117.6 V597.87 V (124.56%)470835.6 WDrop/Amp High
8 AWG8.37 mm²50 A227.78 V (47.45%)252.2 V375.72 V (78.28%)295889.5 WDrop/Amp High
6 AWG13.3 mm²65 A143.34 V (29.86%)336.7 V236.45 V (49.26%)186210.2 WDrop/Amp High
4 AWG21.15 mm²85 A90.14 V (18.78%)389.9 V148.69 V (30.98%)117096.7 WDrop/Amp High
3 AWG26.67 mm²100 A71.48 V (14.89%)408.5 V117.92 V (24.57%)92860.7 WDrop/Amp High
2 AWG33.62 mm²115 A56.71 V (11.81%)423.3 V93.54 V (19.49%)73664.3 WDrop/Amp High
1 AWG42.41 mm²130 A44.95 V (9.37%)435.0 V74.15 V (15.45%)58396.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.64 V (7.43%)444.4 V58.79 V (12.25%)46300.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.27 V (5.89%)451.7 V46.64 V (9.72%)36728.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.43 V (4.67%)457.6 V36.99 V (7.71%)29133.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.78 V (3.71%)462.2 V29.34 V (6.11%)23102.6 WDrop/Amp High
250 kcmil126.7 mm²255 A15.05 V (3.13%)465.0 V24.82 V (5.17%)19546.9 WDrop/Amp High
300 kcmil152.0 mm²285 A12.54 V (2.61%)467.5 V20.69 V (4.31%)16293.4 WDrop/Amp High
350 kcmil177.3 mm²310 A10.75 V (2.24%)469.2 V17.74 V (3.7%)13968.4 WDrop/Amp High
400 kcmil202.7 mm²335 A9.41 V (1.96%)470.6 V15.51 V (3.23%)12218.0 WDrop/Amp High
500 kcmil253.4 mm²380 A7.52 V (1.57%)472.5 V12.41 V (2.59%)9773.5 WDrop/Amp High
600 kcmil304.0 mm²420 A6.27 V (1.31%)473.7 V10.34 V (2.16%)8146.7 WDrop/Amp High
750 kcmil380.0 mm²475 A5.02 V (1.05%)475.0 V8.28 V (1.72%)6517.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.76 V (0.78%)476.2 V6.21 V (1.29%)4887.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 225 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.88V (0.39%) and delivers 478.1V at the load.

What size aluminum wire is required for 750 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.21V (1.29%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.