🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 450 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.33V (11.94%)
Voltage at Load End117.1 VLoss: 2.9 V (2172.3 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 450 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2116.75 V (1763.96%)0.0 V3491.65 V (2909.7%)1587561.1 WDrop/Amp High
12 AWG3.31 mm²20 A1330.16 V (1108.47%)0.0 V2194.15 V (1828.45%)997621.5 WDrop/Amp High
10 AWG5.26 mm²30 A837.04 V (697.53%)0.0 V1380.73 V (1150.61%)627780.8 WDrop/Amp High
8 AWG8.37 mm²50 A526.03 V (438.35%)0.0 V867.7 V (723.08%)394519.4 WDrop/Amp High
6 AWG13.3 mm²65 A331.04 V (275.87%)0.0 V546.06 V (455.05%)248280.2 WDrop/Amp High
4 AWG21.15 mm²85 A208.17 V (173.48%)0.0 V343.39 V (286.16%)156128.9 WDrop/Amp High
3 AWG26.67 mm²100 A165.09 V (137.57%)0.0 V272.31 V (226.93%)123814.3 WDrop/Amp High
2 AWG33.62 mm²115 A130.96 V (109.13%)0.0 V216.02 V (180.02%)98219.1 WDrop/Amp High
1 AWG42.41 mm²130 A103.82 V (86.51%)16.2 V171.25 V (142.71%)77862.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A82.31 V (68.59%)37.7 V135.78 V (113.15%)61733.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A65.29 V (54.41%)54.7 V107.71 V (89.76%)48971.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A51.79 V (43.16%)68.2 V85.43 V (71.19%)38844.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A41.07 V (34.23%)78.9 V67.75 V (56.46%)30803.4 WDrop/Amp High
250 kcmil126.7 mm²255 A34.75 V (28.96%)85.2 V57.32 V (47.77%)26062.6 WDrop/Amp High
300 kcmil152.0 mm²285 A28.97 V (24.14%)91.0 V47.78 V (39.82%)21724.5 WDrop/Amp High
350 kcmil177.3 mm²310 A24.83 V (20.69%)95.2 V40.96 V (34.14%)18624.5 WDrop/Amp High
400 kcmil202.7 mm²335 A21.72 V (18.1%)98.3 V35.83 V (29.86%)16290.7 WDrop/Amp High
500 kcmil253.4 mm²380 A17.38 V (14.48%)102.6 V28.66 V (23.88%)13031.3 WDrop/Amp High
600 kcmil304.0 mm²420 A14.48 V (12.07%)105.5 V23.89 V (19.91%)10862.3 WDrop/Amp High
750 kcmil380.0 mm²475 A11.59 V (9.66%)108.4 V19.11 V (15.93%)8689.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.69 V (7.24%)111.3 V14.33 V (11.94%)6516.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 450 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 450 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.9V (2.41%) and delivers 117.1V at the load.

What size aluminum wire is required for 750 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.33V (11.94%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.