⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.0%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.98V (3.32%)
Voltage at Load End118.8 VLoss: 1.21 V (905.1 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A587.99 V (489.99%)0.0 V969.9 V (808.25%)440989.2 WDrop/Amp High
12 AWG3.31 mm²20 A369.49 V (307.91%)0.0 V609.48 V (507.9%)277117.1 WDrop/Amp High
10 AWG5.26 mm²30 A232.51 V (193.76%)0.0 V383.54 V (319.61%)174383.6 WDrop/Amp High
8 AWG8.37 mm²50 A146.12 V (121.77%)0.0 V241.03 V (200.86%)109588.7 WDrop/Amp High
6 AWG13.3 mm²65 A91.96 V (76.63%)28.0 V151.68 V (126.4%)68966.7 WDrop/Amp High
4 AWG21.15 mm²85 A57.83 V (48.19%)62.2 V95.39 V (79.49%)43369.1 WDrop/Amp High
3 AWG26.67 mm²100 A45.86 V (38.21%)74.1 V75.64 V (63.04%)34392.9 WDrop/Amp High
2 AWG33.62 mm²115 A36.38 V (30.31%)83.6 V60.01 V (50.0%)27283.1 WDrop/Amp High
1 AWG42.41 mm²130 A28.84 V (24.03%)91.2 V47.57 V (39.64%)21628.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.86 V (19.05%)97.1 V37.72 V (31.43%)17148.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.14 V (15.11%)101.9 V29.92 V (24.93%)13603.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.39 V (11.99%)105.6 V23.73 V (19.78%)10790.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.41 V (9.51%)108.6 V18.82 V (15.68%)8556.5 WDrop/Amp High
250 kcmil126.7 mm²255 A9.65 V (8.04%)110.3 V15.92 V (13.27%)7239.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.05 V (6.71%)112.0 V13.27 V (11.06%)6034.6 WDrop/Amp High
350 kcmil177.3 mm²310 A6.9 V (5.75%)113.1 V11.38 V (9.48%)5173.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.03 V (5.03%)114.0 V9.95 V (8.29%)4525.2 WDrop/Amp High
500 kcmil253.4 mm²380 A4.83 V (4.02%)115.2 V7.96 V (6.63%)3619.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.02 V (3.35%)116.0 V6.64 V (5.53%)3017.3 WDrop/Amp High
750 kcmil380.0 mm²475 A3.22 V (2.68%)116.8 V5.31 V (4.42%)2413.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.41 V (2.01%)117.6 V3.98 V (3.32%)1810.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 125 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.21V (1.0%) and delivers 118.8V at the load.

What size aluminum wire is required for 750 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.98V (3.32%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.