⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.65%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.55V (2.12%)
Voltage at Load End119.2 VLoss: 0.77 V (579.3 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A376.31 V (313.59%)0.0 V620.74 V (517.28%)282233.1 WDrop/Amp High
12 AWG3.31 mm²20 A236.47 V (197.06%)0.0 V390.07 V (325.06%)177354.9 WDrop/Amp High
10 AWG5.26 mm²30 A148.81 V (124.01%)0.0 V245.46 V (204.55%)111605.5 WDrop/Amp High
8 AWG8.37 mm²50 A93.52 V (77.93%)26.5 V154.26 V (128.55%)70136.8 WDrop/Amp High
6 AWG13.3 mm²65 A58.85 V (49.04%)61.1 V97.08 V (80.9%)44138.7 WDrop/Amp High
4 AWG21.15 mm²85 A37.01 V (30.84%)83.0 V61.05 V (50.87%)27756.3 WDrop/Amp High
3 AWG26.67 mm²100 A29.35 V (24.46%)90.7 V48.41 V (40.34%)22011.4 WDrop/Amp High
2 AWG33.62 mm²115 A23.28 V (19.4%)96.7 V38.4 V (32.0%)17461.2 WDrop/Amp High
1 AWG42.41 mm²130 A18.46 V (15.38%)101.5 V30.44 V (25.37%)13842.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.63 V (12.19%)105.4 V24.14 V (20.11%)10974.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.61 V (9.67%)108.4 V19.15 V (15.96%)8706.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.21 V (7.67%)110.8 V15.19 V (12.66%)6905.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.3 V (6.08%)112.7 V12.04 V (10.04%)5476.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.18 V (5.15%)113.8 V10.19 V (8.49%)4633.3 WDrop/Amp High
300 kcmil152.0 mm²285 A5.15 V (4.29%)114.9 V8.49 V (7.08%)3862.1 WDrop/Amp High
350 kcmil177.3 mm²310 A4.41 V (3.68%)115.6 V7.28 V (6.07%)3311.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.86 V (3.22%)116.1 V6.37 V (5.31%)2896.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.09 V (2.57%)116.9 V5.1 V (4.25%)2316.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.57 V (2.15%)117.4 V4.25 V (3.54%)1931.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.06 V (1.72%)117.9 V3.4 V (2.83%)1544.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.54 V (1.29%)118.5 V2.55 V (2.12%)1158.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 80 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.77V (0.65%) and delivers 119.2V at the load.

What size aluminum wire is required for 750 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.55V (2.12%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.