750 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.3%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.69V (4.31%)
Voltage at Load End473.7 VLoss: 6.27 V (8146.1 W)
Power & Breaker (125%)623.54 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3055.26 V (636.51%)0.0 V5039.76 V (1049.95%)3968902.6 WDrop/Amp High
12 AWG3.31 mm²20 A1919.92 V (399.98%)0.0 V3166.98 V (659.79%)2494053.6 WDrop/Amp High
10 AWG5.26 mm²30 A1208.16 V (251.7%)0.0 V1992.91 V (415.19%)1569452.0 WDrop/Amp High
8 AWG8.37 mm²50 A759.25 V (158.18%)0.0 V1252.41 V (260.92%)986298.4 WDrop/Amp High
6 AWG13.3 mm²65 A477.82 V (99.54%)2.2 V788.17 V (164.2%)620700.6 WDrop/Amp High
4 AWG21.15 mm²85 A300.47 V (62.6%)179.5 V495.64 V (103.26%)390322.3 WDrop/Amp High
3 AWG26.67 mm²100 A238.28 V (49.64%)241.7 V393.05 V (81.89%)309535.7 WDrop/Amp High
2 AWG33.62 mm²115 A189.02 V (39.38%)291.0 V311.8 V (64.96%)245547.8 WDrop/Amp High
1 AWG42.41 mm²130 A149.85 V (31.22%)330.2 V247.18 V (51.49%)194655.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.81 V (24.75%)361.2 V195.97 V (40.83%)154333.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A94.25 V (19.63%)385.8 V155.46 V (32.39%)122428.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.76 V (15.57%)405.2 V123.31 V (25.69%)97110.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.28 V (12.35%)420.7 V97.79 V (20.37%)77008.6 WDrop/Amp High
250 kcmil126.7 mm²255 A50.16 V (10.45%)429.8 V82.74 V (17.24%)65156.4 WDrop/Amp High
300 kcmil152.0 mm²285 A41.81 V (8.71%)438.2 V68.97 V (14.37%)54311.3 WDrop/Amp High
350 kcmil177.3 mm²310 A35.84 V (7.47%)444.2 V59.12 V (12.32%)46561.3 WDrop/Amp High
400 kcmil202.7 mm²335 A31.35 V (6.53%)448.6 V51.72 V (10.77%)40726.8 WDrop/Amp High
500 kcmil253.4 mm²380 A25.08 V (5.22%)454.9 V41.37 V (8.62%)32578.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.9 V (4.36%)459.1 V34.48 V (7.18%)27155.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.72 V (3.48%)463.3 V27.59 V (5.75%)21724.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.54 V (2.61%)467.5 V20.69 V (4.31%)16292.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 750 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.27V (1.3%) and delivers 473.7V at the load.

What size aluminum wire is required for 750 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.69V (4.31%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.