⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.27V (2.26%)
Voltage at Load End11.7 VLoss: 0.33 V (26.4 W)
Power & Breaker (125%)0.96 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.14 V (334.5%)0.0 V66.21 V (551.77%)3211.2 WDrop/Amp High
12 AWG3.31 mm²20 A25.22 V (210.2%)0.0 V41.61 V (346.73%)2017.9 WDrop/Amp High
10 AWG5.26 mm²30 A15.87 V (132.27%)0.0 V26.18 V (218.19%)1269.8 WDrop/Amp High
8 AWG8.37 mm²50 A9.98 V (83.13%)2.0 V16.45 V (137.12%)798.0 WDrop/Amp High
6 AWG13.3 mm²65 A6.28 V (52.31%)5.7 V10.35 V (86.29%)502.2 WDrop/Amp High
4 AWG21.15 mm²85 A3.95 V (32.9%)8.1 V6.51 V (54.26%)315.8 WDrop/Amp High
3 AWG26.67 mm²100 A3.13 V (26.09%)8.9 V5.16 V (43.03%)250.4 WDrop/Amp High
2 AWG33.62 mm²115 A2.48 V (20.69%)9.5 V4.1 V (34.14%)198.7 WDrop/Amp High
1 AWG42.41 mm²130 A1.97 V (16.41%)10.0 V3.25 V (27.06%)157.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.56 V (13.01%)10.4 V2.57 V (21.46%)124.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.24 V (10.32%)10.8 V2.04 V (17.02%)99.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A0.98 V (8.18%)11.0 V1.62 V (13.5%)78.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.78 V (6.49%)11.2 V1.28 V (10.71%)62.3 WDrop/Amp High
250 kcmil126.7 mm²255 A0.66 V (5.49%)11.3 V1.09 V (9.06%)52.7 WDrop/Amp High
300 kcmil152.0 mm²285 A0.55 V (4.58%)11.5 V0.91 V (7.55%)43.9 W~ ≤5%
350 kcmil177.3 mm²310 A0.47 V (3.92%)11.5 V0.78 V (6.47%)37.7 W~ ≤5%
400 kcmil202.7 mm²335 A0.41 V (3.43%)11.6 V0.68 V (5.66%)33.0 W~ ≤5%
500 kcmil253.4 mm²380 A0.33 V (2.75%)11.7 V0.54 V (4.53%)26.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.27 V (2.29%)11.7 V0.45 V (3.78%)22.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (1.83%)11.8 V0.36 V (3.02%)17.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.16 V (1.37%)11.8 V0.27 V (2.26%)13.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 80 feet one-way at 12V (DC), you need 500 kcmil copper wire. This produces a voltage drop of 0.33V (2.75%) and delivers 11.7V at the load.

What size aluminum wire is required for 80 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.27V (2.26%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.