🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.41V (3.4%)
Voltage at Load End11.7 VLoss: 0.33 V (26.4 W)
Power & Breaker (125%)0.96 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A60.21 V (501.75%)0.0 V99.32 V (827.65%)4816.8 WDrop/Amp High
12 AWG3.31 mm²20 A37.84 V (315.3%)0.0 V62.41 V (520.09%)3026.9 WDrop/Amp High
10 AWG5.26 mm²30 A23.81 V (198.41%)0.0 V39.27 V (327.28%)1904.7 WDrop/Amp High
8 AWG8.37 mm²50 A14.96 V (124.69%)0.0 V24.68 V (205.68%)1197.0 WDrop/Amp High
6 AWG13.3 mm²65 A9.42 V (78.47%)2.6 V15.53 V (129.44%)753.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.92 V (49.34%)6.1 V9.77 V (81.4%)473.7 WDrop/Amp High
3 AWG26.67 mm²100 A4.7 V (39.13%)7.3 V7.75 V (64.55%)375.7 WDrop/Amp High
2 AWG33.62 mm²115 A3.73 V (31.04%)8.3 V6.14 V (51.2%)298.0 WDrop/Amp High
1 AWG42.41 mm²130 A2.95 V (24.61%)9.0 V4.87 V (40.59%)236.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.34 V (19.51%)9.7 V3.86 V (32.18%)187.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.86 V (15.48%)10.1 V3.06 V (25.53%)148.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.47 V (12.28%)10.5 V2.43 V (20.25%)117.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.17 V (9.74%)10.8 V1.93 V (16.06%)93.5 WDrop/Amp High
250 kcmil126.7 mm²255 A0.99 V (8.24%)11.0 V1.63 V (13.59%)79.1 WDrop/Amp High
300 kcmil152.0 mm²285 A0.82 V (6.87%)11.2 V1.36 V (11.33%)65.9 WDrop/Amp High
350 kcmil177.3 mm²310 A0.71 V (5.89%)11.3 V1.17 V (9.71%)56.5 WDrop/Amp High
400 kcmil202.7 mm²335 A0.62 V (5.15%)11.4 V1.02 V (8.49%)49.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.49 V (4.12%)11.5 V0.82 V (6.79%)39.5 W~ ≤5%
600 kcmil304.0 mm²420 A0.41 V (3.43%)11.6 V0.68 V (5.66%)33.0 W~ ≤5%
750 kcmil380.0 mm²475 A0.33 V (2.75%)11.7 V0.54 V (4.53%)26.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (2.06%)11.8 V0.41 V (3.4%)19.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 120 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.33V (2.75%) and delivers 11.7V at the load.

What size aluminum wire is required for 80 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.41V (3.4%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.