🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.68V (0.57%)
Voltage at Load End119.8 VLoss: 0.2 V (164.8 W)
Power & Breaker (125%)96.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A100.35 V (83.62%)19.7 V165.53 V (137.94%)80279.6 WDrop/Amp High
12 AWG3.31 mm²20 A63.06 V (52.55%)56.9 V104.02 V (86.68%)50447.6 WDrop/Amp High
10 AWG5.26 mm²30 A39.68 V (33.07%)80.3 V65.46 V (54.55%)31745.6 WDrop/Amp High
8 AWG8.37 mm²50 A24.94 V (20.78%)95.1 V41.14 V (34.28%)19950.0 WDrop/Amp High
6 AWG13.3 mm²65 A15.69 V (13.08%)104.3 V25.89 V (21.57%)12555.0 WDrop/Amp High
4 AWG21.15 mm²85 A9.87 V (8.22%)110.1 V16.28 V (13.57%)7895.1 WDrop/Amp High
3 AWG26.67 mm²100 A7.83 V (6.52%)112.2 V12.91 V (10.76%)6261.0 WDrop/Amp High
2 AWG33.62 mm²115 A6.21 V (5.17%)113.8 V10.24 V (8.53%)4966.7 WDrop/Amp High
1 AWG42.41 mm²130 A4.92 V (4.1%)115.1 V8.12 V (6.77%)3937.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.9 V (3.25%)116.1 V6.44 V (5.36%)3121.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.1 V (2.58%)116.9 V5.11 V (4.26%)2476.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.46 V (2.05%)117.5 V4.05 V (3.38%)1964.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.95 V (1.62%)118.1 V3.21 V (2.68%)1557.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.65 V (1.37%)118.4 V2.72 V (2.26%)1317.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.37 V (1.14%)118.6 V2.27 V (1.89%)1098.6 WDrop/Amp High
350 kcmil177.3 mm²310 A1.18 V (0.98%)118.8 V1.94 V (1.62%)941.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.03 V (0.86%)119.0 V1.7 V (1.42%)823.8 WDrop/Amp High
500 kcmil253.4 mm²380 A0.82 V (0.69%)119.2 V1.36 V (1.13%)659.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.69 V (0.57%)119.3 V1.13 V (0.94%)549.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.55 V (0.46%)119.5 V0.91 V (0.76%)439.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.41 V (0.34%)119.6 V0.68 V (0.57%)329.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 20 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (0.17%) and delivers 119.8V at the load.

What size aluminum wire is required for 800 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.68V (0.57%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.