🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.72V (2.26%)
Voltage at Load End119.2 VLoss: 0.82 V (659.1 W)
Power & Breaker (125%)96.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A401.4 V (334.5%)0.0 V662.12 V (551.77%)321118.5 WDrop/Amp High
12 AWG3.31 mm²20 A252.24 V (210.2%)0.0 V416.08 V (346.73%)201790.5 WDrop/Amp High
10 AWG5.26 mm²30 A158.73 V (132.27%)0.0 V261.83 V (218.19%)126982.2 WDrop/Amp High
8 AWG8.37 mm²50 A99.75 V (83.13%)20.2 V164.54 V (137.12%)79800.1 WDrop/Amp High
6 AWG13.3 mm²65 A62.78 V (52.31%)57.2 V103.55 V (86.29%)50220.0 WDrop/Amp High
4 AWG21.15 mm²85 A39.48 V (32.9%)80.5 V65.12 V (54.26%)31580.5 WDrop/Amp High
3 AWG26.67 mm²100 A31.31 V (26.09%)88.7 V51.64 V (43.03%)25044.1 WDrop/Amp High
2 AWG33.62 mm²115 A24.83 V (20.69%)95.2 V40.96 V (34.14%)19866.9 WDrop/Amp High
1 AWG42.41 mm²130 A19.69 V (16.41%)100.3 V32.47 V (27.06%)15749.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.61 V (13.01%)104.4 V25.75 V (21.46%)12486.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.38 V (10.32%)107.6 V20.42 V (17.02%)9905.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.82 V (8.18%)110.2 V16.2 V (13.5%)7857.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.79 V (6.49%)112.2 V12.85 V (10.71%)6230.7 WDrop/Amp High
250 kcmil126.7 mm²255 A6.59 V (5.49%)113.4 V10.87 V (9.06%)5271.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.49 V (4.58%)114.5 V9.06 V (7.55%)4394.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.71 V (3.92%)115.3 V7.77 V (6.47%)3767.2 WDrop/Amp High
400 kcmil202.7 mm²335 A4.12 V (3.43%)115.9 V6.79 V (5.66%)3295.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.29 V (2.75%)116.7 V5.43 V (4.53%)2635.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.75 V (2.29%)117.3 V4.53 V (3.78%)2197.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.2 V (1.83%)117.8 V3.62 V (3.02%)1757.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.65 V (1.37%)118.4 V2.72 V (2.26%)1318.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 80 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.82V (0.69%) and delivers 119.2V at the load.

What size aluminum wire is required for 800 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.72V (2.26%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.