⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.04V (1.7%)
Voltage at Load End119.4 VLoss: 0.62 V (494.3 W)
Power & Breaker (125%)96.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.05 V (250.87%)0.0 V496.59 V (413.82%)240838.9 WDrop/Amp High
12 AWG3.31 mm²20 A189.18 V (157.65%)0.0 V312.06 V (260.05%)151342.9 WDrop/Amp High
10 AWG5.26 mm²30 A119.05 V (99.2%)1.0 V196.37 V (163.64%)95236.7 WDrop/Amp High
8 AWG8.37 mm²50 A74.81 V (62.34%)45.2 V123.41 V (102.84%)59850.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.08 V (39.23%)72.9 V77.66 V (64.72%)37665.0 WDrop/Amp High
4 AWG21.15 mm²85 A29.61 V (24.67%)90.4 V48.84 V (40.7%)23685.3 WDrop/Amp High
3 AWG26.67 mm²100 A23.48 V (19.57%)96.5 V38.73 V (32.27%)18783.1 WDrop/Amp High
2 AWG33.62 mm²115 A18.63 V (15.52%)101.4 V30.72 V (25.6%)14900.2 WDrop/Amp High
1 AWG42.41 mm²130 A14.76 V (12.3%)105.2 V24.36 V (20.3%)11812.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.71 V (9.76%)108.3 V19.31 V (16.09%)9365.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.29 V (7.74%)110.7 V15.32 V (12.77%)7429.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.37 V (6.14%)112.6 V12.15 V (10.13%)5892.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.84 V (4.87%)114.2 V9.64 V (8.03%)4673.0 WDrop/Amp High
250 kcmil126.7 mm²255 A4.94 V (4.12%)115.1 V8.15 V (6.79%)3953.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.12 V (3.43%)115.9 V6.8 V (5.66%)3295.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.53 V (2.94%)116.5 V5.83 V (4.85%)2825.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.09 V (2.57%)116.9 V5.1 V (4.25%)2471.4 WDrop/Amp High
500 kcmil253.4 mm²380 A2.47 V (2.06%)117.5 V4.08 V (3.4%)1976.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.06 V (1.72%)117.9 V3.4 V (2.83%)1647.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.65 V (1.37%)118.4 V2.72 V (2.27%)1318.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.24 V (1.03%)118.8 V2.04 V (1.7%)988.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 60 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.62V (0.52%) and delivers 119.4V at the load.

What size aluminum wire is required for 800 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.04V (1.7%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.