🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 100 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.4V (2.83%)
Voltage at Load End119.0 VLoss: 1.03 V (823.9 W)
Power & Breaker (125%)96.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 100 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A501.75 V (418.12%)0.0 V827.65 V (689.71%)401398.2 WDrop/Amp High
12 AWG3.31 mm²20 A315.3 V (262.75%)0.0 V520.09 V (433.41%)252238.1 WDrop/Amp High
10 AWG5.26 mm²30 A198.41 V (165.34%)0.0 V327.28 V (272.74%)158727.8 WDrop/Amp High
8 AWG8.37 mm²50 A124.69 V (103.91%)0.0 V205.68 V (171.4%)99750.1 WDrop/Amp High
6 AWG13.3 mm²65 A78.47 V (65.39%)41.5 V129.44 V (107.86%)62775.0 WDrop/Amp High
4 AWG21.15 mm²85 A49.34 V (41.12%)70.7 V81.4 V (67.83%)39475.6 WDrop/Amp High
3 AWG26.67 mm²100 A39.13 V (32.61%)80.9 V64.55 V (53.79%)31305.1 WDrop/Amp High
2 AWG33.62 mm²115 A31.04 V (25.87%)89.0 V51.2 V (42.67%)24833.7 WDrop/Amp High
1 AWG42.41 mm²130 A24.61 V (20.51%)95.4 V40.59 V (33.83%)19686.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.51 V (16.26%)100.5 V32.18 V (26.82%)15608.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.48 V (12.9%)104.5 V25.53 V (21.28%)12381.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.28 V (10.23%)107.7 V20.25 V (16.88%)9821.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.74 V (8.11%)110.3 V16.06 V (13.38%)7788.3 WDrop/Amp High
250 kcmil126.7 mm²255 A8.24 V (6.86%)111.8 V13.59 V (11.32%)6589.6 WDrop/Amp High
300 kcmil152.0 mm²285 A6.87 V (5.72%)113.1 V11.33 V (9.44%)5492.8 WDrop/Amp High
350 kcmil177.3 mm²310 A5.89 V (4.91%)114.1 V9.71 V (8.09%)4709.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.15 V (4.29%)114.9 V8.49 V (7.08%)4118.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.12 V (3.43%)115.9 V6.79 V (5.66%)3294.8 WDrop/Amp High
600 kcmil304.0 mm²420 A3.43 V (2.86%)116.6 V5.66 V (4.72%)2746.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.75 V (2.29%)117.3 V4.53 V (3.78%)2197.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.06 V (1.72%)117.9 V3.4 V (2.83%)1647.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 100 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 100 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.03V (0.86%) and delivers 119.0V at the load.

What size aluminum wire is required for 800 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.4V (2.83%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.