🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.46V (3.82%)
Voltage at Load End11.7 VLoss: 0.28 V (25.0 W)
Power & Breaker (125%)1.08 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.74 V (564.47%)0.0 V111.73 V (931.11%)6096.2 WDrop/Amp High
12 AWG3.31 mm²20 A42.57 V (354.71%)0.0 V70.21 V (585.11%)3830.9 WDrop/Amp High
10 AWG5.26 mm²30 A26.79 V (223.21%)0.0 V44.18 V (368.19%)2410.7 WDrop/Amp High
8 AWG8.37 mm²50 A16.83 V (140.27%)0.0 V27.77 V (231.39%)1515.0 WDrop/Amp High
6 AWG13.3 mm²65 A10.59 V (88.28%)1.4 V17.47 V (145.62%)953.4 WDrop/Amp High
4 AWG21.15 mm²85 A6.66 V (55.51%)5.3 V10.99 V (91.57%)599.5 WDrop/Amp High
3 AWG26.67 mm²100 A5.28 V (44.02%)6.7 V8.71 V (72.62%)475.4 WDrop/Amp High
2 AWG33.62 mm²115 A4.19 V (34.92%)7.8 V6.91 V (57.61%)377.2 WDrop/Amp High
1 AWG42.41 mm²130 A3.32 V (27.68%)8.7 V5.48 V (45.67%)299.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.63 V (21.95%)9.4 V4.34 V (36.21%)237.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.09 V (17.41%)9.9 V3.45 V (28.72%)188.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.66 V (13.81%)10.3 V2.73 V (22.78%)149.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.31 V (10.95%)10.7 V2.17 V (18.07%)118.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.11 V (9.27%)10.9 V1.83 V (15.29%)100.1 WDrop/Amp High
300 kcmil152.0 mm²285 A0.93 V (7.72%)11.1 V1.53 V (12.74%)83.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.79 V (6.62%)11.2 V1.31 V (10.92%)71.5 WDrop/Amp High
400 kcmil202.7 mm²335 A0.7 V (5.79%)11.3 V1.15 V (9.55%)62.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.56 V (4.63%)11.4 V0.92 V (7.64%)50.0 W~ ≤5%
600 kcmil304.0 mm²420 A0.46 V (3.86%)11.5 V0.76 V (6.37%)41.7 W~ ≤5%
750 kcmil380.0 mm²475 A0.37 V (3.09%)11.6 V0.61 V (5.1%)33.4 W~ ≤5%
1000 kcmil506.7 mm²545 A0.28 V (2.32%)11.7 V0.46 V (3.82%)25.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 120 feet one-way at 12V (DC), you need 1000 kcmil copper wire. This produces a voltage drop of 0.28V (2.32%) and delivers 11.7V at the load.

What size aluminum wire is required for 90 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.46V (3.82%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.