⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)2 AWGDrop: 1.15V (0.48%)
Voltage at Load End239.1 VLoss: 0.88 V (79.2 W)
Power & Breaker (125%)21.6 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A11.29 V (4.7%)228.7 V18.62 V (7.76%)1016.0 WDrop/Amp High
12 AWG3.31 mm²20 A7.09 V (2.96%)232.9 V11.7 V (4.88%)638.5 WDrop/Amp High
10 AWG5.26 mm²30 A4.46 V (1.86%)235.5 V7.36 V (3.07%)401.8 WDrop/Amp High
8 AWG8.37 mm²50 A2.81 V (1.17%)237.2 V4.63 V (1.93%)252.5 WDrop/Amp High
6 AWG13.3 mm²65 A1.77 V (0.74%)238.2 V2.91 V (1.21%)158.9 WDrop/Amp High
4 AWG21.15 mm²85 A1.11 V (0.46%)238.9 V1.83 V (0.76%)99.9 WDrop/Amp High
3 AWG26.67 mm²100 A0.88 V (0.37%)239.1 V1.45 V (0.61%)79.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.7 V (0.29%)239.3 V1.15 V (0.48%)62.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.55 V (0.23%)239.4 V0.91 V (0.38%)49.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.44 V (0.18%)239.6 V0.72 V (0.3%)39.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.35 V (0.15%)239.7 V0.57 V (0.24%)31.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.28 V (0.12%)239.7 V0.46 V (0.19%)24.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.22 V (0.09%)239.8 V0.36 V (0.15%)19.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.19 V (0.08%)239.8 V0.31 V (0.13%)16.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.06%)239.8 V0.25 V (0.11%)13.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.06%)239.9 V0.22 V (0.09%)11.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.12 V (0.05%)239.9 V0.19 V (0.08%)10.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.04%)239.9 V0.15 V (0.06%)8.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.03%)239.9 V0.13 V (0.05%)7.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.03%)239.9 V0.1 V (0.04%)5.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)240.0 V0.08 V (0.03%)4.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 20 feet one-way at 240V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 0.88V (0.37%) and delivers 239.1V at the load.

What size aluminum wire is required for 90 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 1.15V (0.48%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.