90 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.2%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.91V (2.88%)
Voltage at Load End234.7 VLoss: 5.28 V (475.4 W)
Power & Breaker (125%)21.6 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A67.74 V (28.22%)172.3 V111.73 V (46.56%)6096.2 WDrop/Amp High
12 AWG3.31 mm²20 A42.57 V (17.74%)197.4 V70.21 V (29.26%)3830.9 WDrop/Amp High
10 AWG5.26 mm²30 A26.79 V (11.16%)213.2 V44.18 V (18.41%)2410.7 WDrop/Amp High
8 AWG8.37 mm²50 A16.83 V (7.01%)223.2 V27.77 V (11.57%)1515.0 WDrop/Amp High
6 AWG13.3 mm²65 A10.59 V (4.41%)229.4 V17.47 V (7.28%)953.4 WDrop/Amp High
4 AWG21.15 mm²85 A6.66 V (2.78%)233.3 V10.99 V (4.58%)599.5 WDrop/Amp High
3 AWG26.67 mm²100 A5.28 V (2.2%)234.7 V8.71 V (3.63%)475.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.19 V (1.75%)235.8 V6.91 V (2.88%)377.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.32 V (1.38%)236.7 V5.48 V (2.28%)299.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.63 V (1.1%)237.4 V4.34 V (1.81%)237.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.09 V (0.87%)237.9 V3.45 V (1.44%)188.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.66 V (0.69%)238.3 V2.73 V (1.14%)149.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.31 V (0.55%)238.7 V2.17 V (0.9%)118.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.11 V (0.46%)238.9 V1.83 V (0.76%)100.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.93 V (0.39%)239.1 V1.53 V (0.64%)83.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.79 V (0.33%)239.2 V1.31 V (0.55%)71.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.7 V (0.29%)239.3 V1.15 V (0.48%)62.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.56 V (0.23%)239.4 V0.92 V (0.38%)50.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.46 V (0.19%)239.5 V0.76 V (0.32%)41.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.37 V (0.15%)239.6 V0.61 V (0.25%)33.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.12%)239.7 V0.46 V (0.19%)25.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 120 feet one-way at 240V (1-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.28V (2.2%) and delivers 234.7V at the load.

What size aluminum wire is required for 90 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.91V (2.88%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.