🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.99%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.62V (2.76%)
Voltage at Load End232.8 VLoss: 7.18 V (1118.7 W)
Power & Breaker (125%)37.41 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.31 V (122.21%)0.0 V483.82 V (201.59%)45721.8 WDrop/Amp High
12 AWG3.31 mm²20 A184.31 V (76.8%)55.7 V304.03 V (126.68%)28731.5 WDrop/Amp High
10 AWG5.26 mm²30 A115.98 V (48.33%)124.0 V191.32 V (79.72%)18080.1 WDrop/Amp High
8 AWG8.37 mm²50 A72.89 V (30.37%)167.1 V120.23 V (50.1%)11362.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.87 V (19.11%)194.1 V75.66 V (31.53%)7150.5 WDrop/Amp High
4 AWG21.15 mm²85 A28.85 V (12.02%)211.2 V47.58 V (19.83%)4496.5 WDrop/Amp High
3 AWG26.67 mm²100 A22.87 V (9.53%)217.1 V37.73 V (15.72%)3565.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.15 V (7.56%)221.9 V29.93 V (12.47%)2828.7 WDrop/Amp High
1 AWG42.41 mm²130 A14.39 V (5.99%)225.6 V23.73 V (9.89%)2242.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.41 V (4.75%)228.6 V18.81 V (7.84%)1777.9 W~ ≤5%
2/0 AWG67.43 mm²175 A9.05 V (3.77%)231.0 V14.92 V (6.22%)1410.4 W~ ≤5%
3/0 AWG85.01 mm²200 A7.18 V (2.99%)232.8 V11.84 V (4.93%)1118.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.69 V (2.37%)234.3 V9.39 V (3.91%)887.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.82 V (2.01%)235.2 V7.94 V (3.31%)750.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.01 V (1.67%)236.0 V6.62 V (2.76%)625.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.44 V (1.43%)236.6 V5.68 V (2.36%)536.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.01 V (1.25%)237.0 V4.96 V (2.07%)469.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.41 V (1.0%)237.6 V3.97 V (1.65%)375.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.01 V (0.84%)238.0 V3.31 V (1.38%)312.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.61 V (0.67%)238.4 V2.65 V (1.1%)250.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.2 V (0.5%)238.8 V1.99 V (0.83%)187.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 600 feet one-way at 240V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 7.18V (2.99%) and delivers 232.8V at the load.

What size aluminum wire is required for 90 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.62V (2.76%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.