🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.2%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.76V (0.64%)
Voltage at Load End119.8 VLoss: 0.23 V (208.6 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A112.89 V (94.08%)7.1 V186.22 V (155.18%)101603.9 WDrop/Amp High
12 AWG3.31 mm²20 A70.94 V (59.12%)49.1 V117.02 V (97.52%)63847.8 WDrop/Amp High
10 AWG5.26 mm²30 A44.64 V (37.2%)75.4 V73.64 V (61.37%)40178.0 WDrop/Amp High
8 AWG8.37 mm²50 A28.05 V (23.38%)91.9 V46.28 V (38.56%)25249.2 WDrop/Amp High
6 AWG13.3 mm²65 A17.66 V (14.71%)102.3 V29.12 V (24.27%)15889.9 WDrop/Amp High
4 AWG21.15 mm²85 A11.1 V (9.25%)108.9 V18.31 V (15.26%)9992.3 WDrop/Amp High
3 AWG26.67 mm²100 A8.8 V (7.34%)111.2 V14.52 V (12.1%)7924.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.98 V (5.82%)113.0 V11.52 V (9.6%)6286.0 WDrop/Amp High
1 AWG42.41 mm²130 A5.54 V (4.61%)114.5 V9.13 V (7.61%)4983.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.39 V (3.66%)115.6 V7.24 V (6.03%)3950.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.48 V (2.9%)116.5 V5.74 V (4.79%)3134.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.76 V (2.3%)117.2 V4.56 V (3.8%)2486.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.19 V (1.83%)117.8 V3.61 V (3.01%)1971.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.85 V (1.54%)118.1 V3.06 V (2.55%)1668.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.54 V (1.29%)118.5 V2.55 V (2.12%)1390.4 WDrop/Amp High
350 kcmil177.3 mm²310 A1.32 V (1.1%)118.7 V2.18 V (1.82%)1192.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.16 V (0.97%)118.8 V1.91 V (1.59%)1042.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.93 V (0.77%)119.1 V1.53 V (1.27%)834.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.77 V (0.64%)119.2 V1.27 V (1.06%)695.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.62 V (0.51%)119.4 V1.02 V (0.85%)556.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.46 V (0.39%)119.5 V0.76 V (0.64%)417.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 20 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.23V (0.2%) and delivers 119.8V at the load.

What size aluminum wire is required for 900 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.76V (0.64%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.