🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.45%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.73V (4.78%)
Voltage at Load End118.3 VLoss: 1.74 V (1564.0 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A846.7 V (705.58%)0.0 V1396.66 V (1163.88%)762029.3 WDrop/Amp High
12 AWG3.31 mm²20 A532.06 V (443.39%)0.0 V877.66 V (731.38%)478858.3 WDrop/Amp High
10 AWG5.26 mm²30 A334.82 V (279.01%)0.0 V552.29 V (460.24%)301334.8 WDrop/Amp High
8 AWG8.37 mm²50 A210.41 V (175.34%)0.0 V347.08 V (289.23%)189369.3 WDrop/Amp High
6 AWG13.3 mm²65 A132.42 V (110.35%)0.0 V218.42 V (182.02%)119174.5 WDrop/Amp High
4 AWG21.15 mm²85 A83.27 V (69.39%)36.7 V137.35 V (114.46%)74941.9 WDrop/Amp High
3 AWG26.67 mm²100 A66.03 V (55.03%)54.0 V108.93 V (90.77%)59430.9 WDrop/Amp High
2 AWG33.62 mm²115 A52.38 V (43.65%)67.6 V86.41 V (72.01%)47145.2 WDrop/Amp High
1 AWG42.41 mm²130 A41.53 V (34.61%)78.5 V68.5 V (57.08%)37373.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.92 V (27.44%)87.1 V54.31 V (45.26%)29632.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.12 V (21.76%)93.9 V43.08 V (35.9%)23506.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.72 V (17.26%)99.3 V34.17 V (28.48%)18645.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.43 V (13.69%)103.6 V27.1 V (22.58%)14785.6 WDrop/Amp High
250 kcmil126.7 mm²255 A13.9 V (11.58%)106.1 V22.93 V (19.11%)12510.0 WDrop/Amp High
300 kcmil152.0 mm²285 A11.59 V (9.66%)108.4 V19.11 V (15.93%)10427.8 WDrop/Amp High
350 kcmil177.3 mm²310 A9.93 V (8.28%)110.1 V16.38 V (13.65%)8939.8 WDrop/Amp High
400 kcmil202.7 mm²335 A8.69 V (7.24%)111.3 V14.33 V (11.94%)7819.5 WDrop/Amp High
500 kcmil253.4 mm²380 A6.95 V (5.79%)113.0 V11.46 V (9.55%)6255.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.79 V (4.83%)114.2 V9.56 V (7.96%)5213.9 WDrop/Amp High
750 kcmil380.0 mm²475 A4.63 V (3.86%)115.4 V7.64 V (6.37%)4171.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.48 V (2.9%)116.5 V5.73 V (4.78%)3128.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 150 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.74V (1.45%) and delivers 118.3V at the load.

What size aluminum wire is required for 900 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.73V (4.78%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.