🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.59V (3.82%)
Voltage at Load End118.6 VLoss: 1.39 V (1251.2 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A677.36 V (564.47%)0.0 V1117.33 V (931.11%)609623.4 WDrop/Amp High
12 AWG3.31 mm²20 A425.65 V (354.71%)0.0 V702.13 V (585.11%)383086.6 WDrop/Amp High
10 AWG5.26 mm²30 A267.85 V (223.21%)0.0 V441.83 V (368.19%)241067.8 WDrop/Amp High
8 AWG8.37 mm²50 A168.33 V (140.27%)0.0 V277.66 V (231.39%)151495.4 WDrop/Amp High
6 AWG13.3 mm²65 A105.93 V (88.28%)14.1 V174.74 V (145.62%)95339.6 WDrop/Amp High
4 AWG21.15 mm²85 A66.62 V (55.51%)53.4 V109.88 V (91.57%)59953.5 WDrop/Amp High
3 AWG26.67 mm²100 A52.83 V (44.02%)67.2 V87.14 V (72.62%)47544.7 WDrop/Amp High
2 AWG33.62 mm²115 A41.91 V (34.92%)78.1 V69.13 V (57.61%)37716.1 WDrop/Amp High
1 AWG42.41 mm²130 A33.22 V (27.68%)86.8 V54.8 V (45.67%)29899.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.34 V (21.95%)93.7 V43.45 V (36.21%)23705.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.89 V (17.41%)99.1 V34.47 V (28.72%)18804.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.57 V (13.81%)103.4 V27.34 V (22.78%)14916.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.14 V (10.95%)106.9 V21.68 V (18.07%)11828.5 WDrop/Amp High
250 kcmil126.7 mm²255 A11.12 V (9.27%)108.9 V18.34 V (15.29%)10008.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.27 V (7.72%)110.7 V15.29 V (12.74%)8342.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.95 V (6.62%)112.1 V13.11 V (10.92%)7151.8 WDrop/Amp High
400 kcmil202.7 mm²335 A6.95 V (5.79%)113.0 V11.47 V (9.55%)6255.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.56 V (4.63%)114.4 V9.17 V (7.64%)5004.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.63 V (3.86%)115.4 V7.64 V (6.37%)4171.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.71 V (3.09%)116.3 V6.12 V (5.1%)3336.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.78 V (2.32%)117.2 V4.59 V (3.82%)2502.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 120 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.39V (1.16%) and delivers 118.6V at the load.

What size aluminum wire is required for 900 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.59V (3.82%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.