🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.78V (3.98%)
Voltage at Load End118.5 VLoss: 1.45 V (1303.4 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A705.58 V (587.99%)0.0 V1163.88 V (969.9%)635024.4 WDrop/Amp High
12 AWG3.31 mm²20 A443.39 V (369.49%)0.0 V731.38 V (609.48%)399048.6 WDrop/Amp High
10 AWG5.26 mm²30 A279.01 V (232.51%)0.0 V460.24 V (383.54%)251112.3 WDrop/Amp High
8 AWG8.37 mm²50 A175.34 V (146.12%)0.0 V289.23 V (241.03%)157807.7 WDrop/Amp High
6 AWG13.3 mm²65 A110.35 V (91.96%)9.7 V182.02 V (151.68%)99312.1 WDrop/Amp High
4 AWG21.15 mm²85 A69.39 V (57.83%)50.6 V114.46 V (95.39%)62451.6 WDrop/Amp High
3 AWG26.67 mm²100 A55.03 V (45.86%)65.0 V90.77 V (75.64%)49525.7 WDrop/Amp High
2 AWG33.62 mm²115 A43.65 V (36.38%)76.3 V72.01 V (60.01%)39287.7 WDrop/Amp High
1 AWG42.41 mm²130 A34.61 V (28.84%)85.4 V57.08 V (47.57%)31144.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.44 V (22.86%)92.6 V45.26 V (37.72%)24693.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.76 V (18.14%)98.2 V35.9 V (29.92%)19588.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.26 V (14.39%)102.7 V28.48 V (23.73%)15537.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.69 V (11.41%)106.3 V22.58 V (18.82%)12321.4 WDrop/Amp High
250 kcmil126.7 mm²255 A11.58 V (9.65%)108.4 V19.11 V (15.92%)10425.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.66 V (8.05%)110.3 V15.93 V (13.27%)8689.8 WDrop/Amp High
350 kcmil177.3 mm²310 A8.28 V (6.9%)111.7 V13.65 V (11.38%)7449.8 WDrop/Amp High
400 kcmil202.7 mm²335 A7.24 V (6.03%)112.8 V11.94 V (9.95%)6516.3 WDrop/Amp High
500 kcmil253.4 mm²380 A5.79 V (4.83%)114.2 V9.55 V (7.96%)5212.5 WDrop/Amp High
600 kcmil304.0 mm²420 A4.83 V (4.02%)115.2 V7.96 V (6.64%)4344.9 WDrop/Amp High
750 kcmil380.0 mm²475 A3.86 V (3.22%)116.1 V6.37 V (5.31%)3475.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.9 V (2.41%)117.1 V4.78 V (3.98%)2606.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 125 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.45V (1.21%) and delivers 118.5V at the load.

What size aluminum wire is required for 900 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.78V (3.98%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.