🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.08%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.45V (3.58%)
Voltage at Load End205.7 VLoss: 2.26 V (3519.2 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1099.89 V (528.8%)0.0 V1814.31 V (872.27%)1714565.9 WDrop/Amp High
12 AWG3.31 mm²20 A691.17 V (332.29%)0.0 V1140.11 V (548.13%)1077431.2 WDrop/Amp High
10 AWG5.26 mm²30 A434.94 V (209.11%)0.0 V717.45 V (344.93%)678003.3 WDrop/Amp High
8 AWG8.37 mm²50 A273.33 V (131.41%)0.0 V450.87 V (216.76%)426080.9 WDrop/Amp High
6 AWG13.3 mm²65 A172.01 V (82.7%)36.0 V283.74 V (136.41%)268142.6 WDrop/Amp High
4 AWG21.15 mm²85 A108.17 V (52.0%)99.8 V178.43 V (85.78%)168619.3 WDrop/Amp High
3 AWG26.67 mm²100 A85.78 V (41.24%)122.2 V141.5 V (68.03%)133719.4 WDrop/Amp High
2 AWG33.62 mm²115 A68.05 V (32.72%)140.0 V112.25 V (53.97%)106076.7 WDrop/Amp High
1 AWG42.41 mm²130 A53.94 V (25.93%)154.1 V88.98 V (42.78%)84090.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A42.77 V (20.56%)165.2 V70.55 V (33.92%)66672.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A33.93 V (16.31%)174.1 V55.97 V (26.91%)52888.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A26.91 V (12.94%)181.1 V44.39 V (21.34%)41951.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.34 V (10.26%)186.7 V35.2 V (16.92%)33267.7 WDrop/Amp High
250 kcmil126.7 mm²255 A18.06 V (8.68%)189.9 V29.79 V (14.32%)28147.6 WDrop/Amp High
300 kcmil152.0 mm²285 A15.05 V (7.24%)192.9 V24.83 V (11.94%)23462.5 WDrop/Amp High
350 kcmil177.3 mm²310 A12.9 V (6.2%)195.1 V21.28 V (10.23%)20114.5 WDrop/Amp High
400 kcmil202.7 mm²335 A11.29 V (5.43%)196.7 V18.62 V (8.95%)17594.0 WDrop/Amp High
500 kcmil253.4 mm²380 A9.03 V (4.34%)199.0 V14.89 V (7.16%)14073.8 WDrop/Amp High
600 kcmil304.0 mm²420 A7.53 V (3.62%)200.5 V12.41 V (5.97%)11731.2 WDrop/Amp High
750 kcmil380.0 mm²475 A6.02 V (2.89%)202.0 V9.93 V (4.77%)9385.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.52 V (2.17%)203.5 V7.45 V (3.58%)7038.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 225 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.26V (1.08%) and delivers 205.7V at the load.

What size aluminum wire is required for 900 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.45V (3.58%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.