🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)18× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.51V (87.59%)
Voltage at Load End11.7 VLoss: 0.35 V (318.6 W)
Power & Breaker (125%)10.8 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1552.28 V (12935.68%)0.0 V2560.54 V (21337.83%)1397053.7 WDrop/Amp High
12 AWG3.31 mm²20 A975.45 V (8128.77%)0.0 V1609.04 V (13408.67%)877906.9 WDrop/Amp High
10 AWG5.26 mm²30 A613.83 V (5115.25%)0.0 V1012.53 V (8437.77%)552447.1 WDrop/Amp High
8 AWG8.37 mm²50 A385.75 V (3214.6%)0.0 V636.31 V (5302.59%)347177.0 WDrop/Amp High
6 AWG13.3 mm²65 A242.76 V (2023.02%)0.0 V400.45 V (3337.04%)218486.6 WDrop/Amp High
4 AWG21.15 mm²85 A152.66 V (1272.16%)0.0 V251.82 V (2098.47%)137393.5 WDrop/Amp High
3 AWG26.67 mm²100 A121.06 V (1008.86%)0.0 V199.7 V (1664.14%)108956.6 WDrop/Amp High
2 AWG33.62 mm²115 A96.04 V (800.3%)0.0 V158.42 V (1320.13%)86432.8 WDrop/Amp High
1 AWG42.41 mm²130 A76.13 V (634.43%)0.0 V125.58 V (1046.51%)68518.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.36 V (503.01%)0.0 V99.57 V (829.74%)54325.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.88 V (399.02%)0.0 V78.98 V (658.2%)43094.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.98 V (316.51%)0.0 V62.65 V (522.09%)34182.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.12 V (250.99%)0.0 V49.68 V (414.02%)27107.0 WDrop/Amp High
250 kcmil126.7 mm²255 A25.48 V (212.36%)0.0 V42.04 V (350.3%)22935.1 WDrop/Amp High
300 kcmil152.0 mm²285 A21.24 V (177.01%)0.0 V35.04 V (291.99%)19117.6 WDrop/Amp High
350 kcmil177.3 mm²310 A18.21 V (151.76%)0.0 V30.04 V (250.33%)16389.6 WDrop/Amp High
400 kcmil202.7 mm²335 A15.93 V (132.74%)0.0 V26.27 V (218.96%)14335.8 WDrop/Amp High
500 kcmil253.4 mm²380 A12.74 V (106.18%)0.0 V21.02 V (175.15%)11467.5 WDrop/Amp High
600 kcmil304.0 mm²420 A10.62 V (88.51%)1.4 V17.52 V (146.0%)9558.8 WDrop/Amp High
750 kcmil380.0 mm²475 A8.5 V (70.81%)3.5 V14.02 V (116.8%)7647.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.37 V (53.1%)5.6 V10.51 V (87.59%)5734.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 275 feet one-way at 12V (DC), you need 18× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 900 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.51V (87.59%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.