🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 400 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)26× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.29V (127.41%)
Voltage at Load End11.6 VLoss: 0.36 V (320.8 W)
Power & Breaker (125%)10.8 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 400 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2257.86 V (18815.54%)0.0 V3724.42 V (31036.85%)2032078.2 WDrop/Amp High
12 AWG3.31 mm²20 A1418.84 V (11823.66%)0.0 V2340.42 V (19503.52%)1276955.5 WDrop/Amp High
10 AWG5.26 mm²30 A892.84 V (7440.37%)0.0 V1472.78 V (12273.13%)803559.4 WDrop/Amp High
8 AWG8.37 mm²50 A561.09 V (4675.78%)0.0 V925.54 V (7712.86%)504984.8 WDrop/Amp High
6 AWG13.3 mm²65 A353.11 V (2942.58%)0.0 V582.47 V (4853.88%)317798.7 WDrop/Amp High
4 AWG21.15 mm²85 A222.05 V (1850.42%)0.0 V366.28 V (3052.32%)199845.0 WDrop/Amp High
3 AWG26.67 mm²100 A176.09 V (1467.43%)0.0 V290.47 V (2420.57%)158482.3 WDrop/Amp High
2 AWG33.62 mm²115 A139.69 V (1164.08%)0.0 V230.42 V (1920.19%)125720.5 WDrop/Amp High
1 AWG42.41 mm²130 A110.74 V (922.81%)0.0 V182.66 V (1522.2%)99663.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A87.8 V (731.66%)0.0 V144.83 V (1206.89%)79018.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A69.65 V (580.4%)0.0 V114.89 V (957.39%)62683.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A55.24 V (460.37%)0.0 V91.13 V (759.4%)49720.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A43.81 V (365.08%)0.0 V72.26 V (602.21%)39428.4 WDrop/Amp High
250 kcmil126.7 mm²255 A37.07 V (308.89%)0.0 V61.14 V (509.52%)33360.1 WDrop/Amp High
300 kcmil152.0 mm²285 A30.9 V (257.48%)0.0 V50.97 V (424.71%)27807.4 WDrop/Amp High
350 kcmil177.3 mm²310 A26.49 V (220.74%)0.0 V43.69 V (364.11%)23839.4 WDrop/Amp High
400 kcmil202.7 mm²335 A23.17 V (193.08%)0.0 V38.22 V (318.48%)20852.1 WDrop/Amp High
500 kcmil253.4 mm²380 A18.53 V (154.44%)0.0 V30.57 V (254.76%)16680.0 WDrop/Amp High
600 kcmil304.0 mm²420 A15.45 V (128.74%)0.0 V25.48 V (212.36%)13903.7 WDrop/Amp High
750 kcmil380.0 mm²475 A12.36 V (102.99%)0.0 V20.39 V (169.89%)11123.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.27 V (77.24%)2.7 V15.29 V (127.41%)8341.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 400 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 400 feet one-way at 12V (DC), you need 26× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.97%) and delivers 11.6V at the load.

What size aluminum wire is required for 900 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.29V (127.41%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.