🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)29× 1000 kcmil (Parallel)506.7 mm² · Drop: 3.0%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.2V (143.33%)
Voltage at Load End11.6 VLoss: 0.36 V (323.6 W)
Power & Breaker (125%)10.8 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2540.1 V (21167.48%)0.0 V4189.97 V (34916.45%)2286087.9 WDrop/Amp High
12 AWG3.31 mm²20 A1596.19 V (13301.62%)0.0 V2632.97 V (21941.46%)1436574.9 WDrop/Amp High
10 AWG5.26 mm²30 A1004.45 V (8370.41%)0.0 V1656.87 V (13807.27%)904004.3 WDrop/Amp High
8 AWG8.37 mm²50 A631.23 V (5260.26%)0.0 V1041.24 V (8676.97%)568107.9 WDrop/Amp High
6 AWG13.3 mm²65 A397.25 V (3310.4%)0.0 V655.27 V (5460.62%)357523.5 WDrop/Amp High
4 AWG21.15 mm²85 A249.81 V (2081.72%)0.0 V412.06 V (3433.86%)224825.7 WDrop/Amp High
3 AWG26.67 mm²100 A198.1 V (1650.86%)0.0 V326.78 V (2723.14%)178292.6 WDrop/Amp High
2 AWG33.62 mm²115 A157.15 V (1309.59%)0.0 V259.23 V (2160.21%)141435.5 WDrop/Amp High
1 AWG42.41 mm²130 A124.58 V (1038.16%)0.0 V205.5 V (1712.48%)112121.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A98.77 V (823.11%)0.0 V162.93 V (1357.75%)88896.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A78.35 V (652.95%)0.0 V129.25 V (1077.06%)70518.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A62.15 V (517.92%)0.0 V102.52 V (854.33%)55935.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A49.29 V (410.71%)0.0 V81.3 V (677.48%)44356.9 WDrop/Amp High
250 kcmil126.7 mm²255 A41.7 V (347.5%)0.0 V68.79 V (573.21%)37530.1 WDrop/Amp High
300 kcmil152.0 mm²285 A34.76 V (289.66%)0.0 V57.34 V (477.8%)31283.3 WDrop/Amp High
350 kcmil177.3 mm²310 A29.8 V (248.33%)0.0 V49.15 V (409.62%)26819.3 WDrop/Amp High
400 kcmil202.7 mm²335 A26.07 V (217.21%)0.0 V43.0 V (358.29%)23458.6 WDrop/Amp High
500 kcmil253.4 mm²380 A20.85 V (173.75%)0.0 V34.39 V (286.61%)18765.0 WDrop/Amp High
600 kcmil304.0 mm²420 A17.38 V (144.83%)0.0 V28.67 V (238.9%)15641.7 WDrop/Amp High
750 kcmil380.0 mm²475 A13.9 V (115.86%)0.0 V22.93 V (191.12%)12513.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.43 V (86.89%)1.6 V17.2 V (143.33%)9384.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 450 feet one-way at 12V (DC), you need 29× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (3.0%) and delivers 11.6V at the load.

What size aluminum wire is required for 900 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.2V (143.33%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.