900 Amp Wire Size at 450 Feet (208V Three-Phase (US Commercial Wye))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 450 ft (137.2 m) one-way run.
Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.9V (7.16%)
Voltage at Load End203.5 VLoss: 4.51 V (7038.3 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended
All AWG & kcmil Wire Gauges for 900 Amps at 450 Feet (208V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 2199.79 V (1057.59%) | 0.0 V | 3628.62 V (1744.53%) | 3429131.9 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 1382.34 V (664.59%) | 0.0 V | 2280.22 V (1096.26%) | 2154862.3 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 869.88 V (418.21%) | 0.0 V | 1434.89 V (689.85%) | 1356006.5 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 546.66 V (262.82%) | 0.0 V | 901.74 V (433.53%) | 852161.8 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 344.03 V (165.4%) | 0.0 V | 567.48 V (272.83%) | 536285.3 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 216.34 V (104.01%) | 0.0 V | 356.86 V (171.57%) | 337238.5 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 171.56 V (82.48%) | 36.4 V | 283.0 V (136.06%) | 267438.9 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 136.1 V (65.43%) | 71.9 V | 224.5 V (107.93%) | 212153.3 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 107.89 V (51.87%) | 100.1 V | 177.97 V (85.56%) | 168181.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 85.54 V (41.13%) | 122.5 V | 141.1 V (67.84%) | 133344.4 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 67.86 V (32.62%) | 140.1 V | 111.93 V (53.81%) | 105777.8 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 53.82 V (25.88%) | 154.2 V | 88.78 V (42.68%) | 83903.0 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 42.68 V (20.52%) | 165.3 V | 70.41 V (33.85%) | 66535.4 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 36.11 V (17.36%) | 171.9 V | 59.57 V (28.64%) | 56295.1 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 30.1 V (14.47%) | 177.9 V | 49.65 V (23.87%) | 46925.0 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 25.81 V (12.41%) | 182.2 V | 42.57 V (20.47%) | 40229.0 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 22.57 V (10.85%) | 185.4 V | 37.24 V (17.9%) | 35187.9 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 18.06 V (8.68%) | 189.9 V | 29.79 V (14.32%) | 28147.6 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 15.05 V (7.24%) | 192.9 V | 24.83 V (11.94%) | 23462.5 W | Drop/Amp High |
| 750 kcmil | 380.0 mm² | 475 A | 12.04 V (5.79%) | 196.0 V | 19.86 V (9.55%) | 18770.0 W | Drop/Amp High |
| 1000 kcmil | 506.7 mm² | 545 A | 9.03 V (4.34%) | 199.0 V | 14.9 V (7.16%) | 14076.6 W | Drop/Amp High |
Frequently Asked Engineering Questions
What size copper wire do I need for 900 amps at 450 feet (208V)?
To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 450 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.51V (2.17%) and delivers 203.5V at the load.
What size aluminum wire is required for 900 amps at 450 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.9V (7.16%).
What breaker size is needed for a 900A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.