⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 60 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.29V (0.96%)
Voltage at Load End239.3 VLoss: 0.69 V (625.6 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A338.68 V (141.12%)0.0 V558.66 V (232.78%)304811.7 WDrop/Amp High
12 AWG3.31 mm²20 A212.83 V (88.68%)27.2 V351.06 V (146.28%)191543.3 WDrop/Amp High
10 AWG5.26 mm²30 A133.93 V (55.8%)106.1 V220.92 V (92.05%)120533.9 WDrop/Amp High
8 AWG8.37 mm²50 A84.16 V (35.07%)155.8 V138.83 V (57.85%)75747.7 WDrop/Amp High
6 AWG13.3 mm²65 A52.97 V (22.07%)187.0 V87.37 V (36.4%)47669.8 WDrop/Amp High
4 AWG21.15 mm²85 A33.31 V (13.88%)206.7 V54.94 V (22.89%)29976.8 WDrop/Amp High
3 AWG26.67 mm²100 A26.41 V (11.01%)213.6 V43.57 V (18.15%)23772.3 WDrop/Amp High
2 AWG33.62 mm²115 A20.95 V (8.73%)219.0 V34.56 V (14.4%)18858.1 WDrop/Amp High
1 AWG42.41 mm²130 A16.61 V (6.92%)223.4 V27.4 V (11.42%)14949.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.17 V (5.49%)226.8 V21.72 V (9.05%)11852.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.45 V (4.35%)229.6 V17.23 V (7.18%)9402.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.29 V (3.45%)231.7 V13.67 V (5.7%)7458.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.57 V (2.74%)233.4 V10.84 V (4.52%)5914.3 WDrop/Amp High
250 kcmil126.7 mm²255 A5.56 V (2.32%)234.4 V9.17 V (3.82%)5004.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.63 V (1.93%)235.4 V7.64 V (3.19%)4171.1 WDrop/Amp High
350 kcmil177.3 mm²310 A3.97 V (1.66%)236.0 V6.55 V (2.73%)3575.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.48 V (1.45%)236.5 V5.73 V (2.39%)3127.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.78 V (1.16%)237.2 V4.59 V (1.91%)2502.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.32 V (0.97%)237.7 V3.82 V (1.59%)2085.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.85 V (0.77%)238.1 V3.06 V (1.27%)1668.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.39 V (0.58%)238.6 V2.29 V (0.96%)1251.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 60 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.69V (0.29%) and delivers 239.3V at the load.

What size aluminum wire is required for 900 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.29V (0.96%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.