🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.15V (0.48%)
Voltage at Load End239.7 VLoss: 0.35 V (312.8 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A169.34 V (70.56%)70.7 V279.33 V (116.39%)152405.9 WDrop/Amp High
12 AWG3.31 mm²20 A106.41 V (44.34%)133.6 V175.53 V (73.14%)95771.7 WDrop/Amp High
10 AWG5.26 mm²30 A66.96 V (27.9%)173.0 V110.46 V (46.02%)60267.0 WDrop/Amp High
8 AWG8.37 mm²50 A42.08 V (17.53%)197.9 V69.42 V (28.92%)37873.9 WDrop/Amp High
6 AWG13.3 mm²65 A26.48 V (11.03%)213.5 V43.68 V (18.2%)23834.9 WDrop/Amp High
4 AWG21.15 mm²85 A16.65 V (6.94%)223.3 V27.47 V (11.45%)14988.4 WDrop/Amp High
3 AWG26.67 mm²100 A13.21 V (5.5%)226.8 V21.79 V (9.08%)11886.2 WDrop/Amp High
2 AWG33.62 mm²115 A10.48 V (4.37%)229.5 V17.28 V (7.2%)9429.0 WDrop/Amp High
1 AWG42.41 mm²130 A8.31 V (3.46%)231.7 V13.7 V (5.71%)7474.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.58 V (2.74%)233.4 V10.86 V (4.53%)5926.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.22 V (2.18%)234.8 V8.62 V (3.59%)4701.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.14 V (1.73%)235.9 V6.83 V (2.85%)3729.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.29 V (1.37%)236.7 V5.42 V (2.26%)2957.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.78 V (1.16%)237.2 V4.59 V (1.91%)2502.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.32 V (0.97%)237.7 V3.82 V (1.59%)2085.6 WDrop/Amp High
350 kcmil177.3 mm²310 A1.99 V (0.83%)238.0 V3.28 V (1.37%)1788.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.74 V (0.72%)238.3 V2.87 V (1.19%)1563.9 WDrop/Amp High
500 kcmil253.4 mm²380 A1.39 V (0.58%)238.6 V2.29 V (0.96%)1251.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.16 V (0.48%)238.8 V1.91 V (0.8%)1042.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.93 V (0.39%)239.1 V1.53 V (0.64%)834.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.7 V (0.29%)239.3 V1.15 V (0.48%)625.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 30 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (0.14%) and delivers 239.7V at the load.

What size aluminum wire is required for 900 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.15V (0.48%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.