🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.99V (0.83%)
Voltage at Load End239.4 VLoss: 0.6 V (938.5 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.31 V (122.21%)0.0 V483.82 V (201.59%)457217.6 WDrop/Amp High
12 AWG3.31 mm²20 A184.31 V (76.8%)55.7 V304.03 V (126.68%)287315.0 WDrop/Amp High
10 AWG5.26 mm²30 A115.98 V (48.33%)124.0 V191.32 V (79.72%)180800.9 WDrop/Amp High
8 AWG8.37 mm²50 A72.89 V (30.37%)167.1 V120.23 V (50.1%)113621.6 WDrop/Amp High
6 AWG13.3 mm²65 A45.87 V (19.11%)194.1 V75.66 V (31.53%)71504.7 WDrop/Amp High
4 AWG21.15 mm²85 A28.85 V (12.02%)211.2 V47.58 V (19.83%)44965.1 WDrop/Amp High
3 AWG26.67 mm²100 A22.87 V (9.53%)217.1 V37.73 V (15.72%)35658.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.15 V (7.56%)221.9 V29.93 V (12.47%)28287.1 WDrop/Amp High
1 AWG42.41 mm²130 A14.39 V (5.99%)225.6 V23.73 V (9.89%)22424.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.41 V (4.75%)228.6 V18.81 V (7.84%)17779.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.05 V (3.77%)231.0 V14.92 V (6.22%)14103.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.18 V (2.99%)232.8 V11.84 V (4.93%)11187.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.69 V (2.37%)234.3 V9.39 V (3.91%)8871.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.82 V (2.01%)235.2 V7.94 V (3.31%)7506.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.01 V (1.67%)236.0 V6.62 V (2.76%)6256.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.44 V (1.43%)236.6 V5.68 V (2.36%)5363.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.01 V (1.25%)237.0 V4.96 V (2.07%)4691.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.41 V (1.0%)237.6 V3.97 V (1.65%)3753.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.01 V (0.84%)238.0 V3.31 V (1.38%)3128.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.61 V (0.67%)238.4 V2.65 V (1.1%)2502.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.2 V (0.5%)238.8 V1.99 V (0.83%)1876.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 60 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.6V (0.25%) and delivers 239.4V at the load.

What size aluminum wire is required for 900 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.99V (0.83%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.