⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.97V (1.66%)
Voltage at Load End238.8 VLoss: 1.21 V (1876.9 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A586.61 V (244.42%)0.0 V967.63 V (403.18%)914435.2 WDrop/Amp High
12 AWG3.31 mm²20 A368.63 V (153.59%)0.0 V608.06 V (253.36%)574630.0 WDrop/Amp High
10 AWG5.26 mm²30 A231.97 V (96.65%)8.0 V382.64 V (159.43%)361601.7 WDrop/Amp High
8 AWG8.37 mm²50 A145.78 V (60.74%)94.2 V240.46 V (100.19%)227243.1 WDrop/Amp High
6 AWG13.3 mm²65 A91.74 V (38.23%)148.3 V151.33 V (63.05%)143009.4 WDrop/Amp High
4 AWG21.15 mm²85 A57.69 V (24.04%)182.3 V95.16 V (39.65%)89930.3 WDrop/Amp High
3 AWG26.67 mm²100 A45.75 V (19.06%)194.3 V75.47 V (31.44%)71317.0 WDrop/Amp High
2 AWG33.62 mm²115 A36.29 V (15.12%)203.7 V59.87 V (24.94%)56574.2 WDrop/Amp High
1 AWG42.41 mm²130 A28.77 V (11.99%)211.2 V47.46 V (19.77%)44848.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.81 V (9.5%)217.2 V37.63 V (15.68%)35558.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.1 V (7.54%)221.9 V29.85 V (12.44%)28207.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.35 V (5.98%)225.6 V23.68 V (9.86%)22374.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.38 V (4.74%)228.6 V18.77 V (7.82%)17742.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.63 V (4.01%)230.4 V15.89 V (6.62%)15012.0 WDrop/Amp High
300 kcmil152.0 mm²285 A8.03 V (3.34%)232.0 V13.24 V (5.52%)12513.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.88 V (2.87%)233.1 V11.35 V (4.73%)10727.7 WDrop/Amp High
400 kcmil202.7 mm²335 A6.02 V (2.51%)234.0 V9.93 V (4.14%)9383.4 WDrop/Amp High
500 kcmil253.4 mm²380 A4.82 V (2.01%)235.2 V7.94 V (3.31%)7506.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.01 V (1.67%)236.0 V6.62 V (2.76%)6256.7 WDrop/Amp High
750 kcmil380.0 mm²475 A3.21 V (1.34%)236.8 V5.3 V (2.21%)5005.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.41 V (1.0%)237.6 V3.97 V (1.66%)3753.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 120 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.21V (0.5%) and delivers 238.8V at the load.

What size aluminum wire is required for 900 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.97V (1.66%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.