⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.48V (1.03%)
Voltage at Load End239.2 VLoss: 0.76 V (1173.0 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A366.63 V (152.76%)0.0 V604.77 V (251.99%)571522.0 WDrop/Amp High
12 AWG3.31 mm²20 A230.39 V (96.0%)9.6 V380.04 V (158.35%)359143.7 WDrop/Amp High
10 AWG5.26 mm²30 A144.98 V (60.41%)95.0 V239.15 V (99.65%)226001.1 WDrop/Amp High
8 AWG8.37 mm²50 A91.11 V (37.96%)148.9 V150.29 V (62.62%)142027.0 WDrop/Amp High
6 AWG13.3 mm²65 A57.34 V (23.89%)182.7 V94.58 V (39.41%)89380.9 WDrop/Amp High
4 AWG21.15 mm²85 A36.06 V (15.02%)203.9 V59.48 V (24.78%)56206.4 WDrop/Amp High
3 AWG26.67 mm²100 A28.59 V (11.91%)211.4 V47.17 V (19.65%)44573.1 WDrop/Amp High
2 AWG33.62 mm²115 A22.68 V (9.45%)217.3 V37.42 V (15.59%)35358.9 WDrop/Amp High
1 AWG42.41 mm²130 A17.98 V (7.49%)222.0 V29.66 V (12.36%)28030.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.26 V (5.94%)225.7 V23.52 V (9.8%)22224.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.31 V (4.71%)228.7 V18.66 V (7.77%)17629.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.97 V (3.74%)231.0 V14.8 V (6.17%)13983.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.11 V (2.96%)232.9 V11.73 V (4.89%)11089.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.02 V (2.51%)234.0 V9.93 V (4.14%)9382.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.02 V (2.09%)235.0 V8.28 V (3.45%)7820.8 WDrop/Amp High
350 kcmil177.3 mm²310 A4.3 V (1.79%)235.7 V7.09 V (2.96%)6704.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.76 V (1.57%)236.2 V6.21 V (2.59%)5864.7 WDrop/Amp High
500 kcmil253.4 mm²380 A3.01 V (1.25%)237.0 V4.96 V (2.07%)4691.3 WDrop/Amp High
600 kcmil304.0 mm²420 A2.51 V (1.05%)237.5 V4.14 V (1.72%)3910.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.01 V (0.84%)238.0 V3.31 V (1.38%)3128.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.51 V (0.63%)238.5 V2.48 V (1.03%)2346.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 75 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.76V (0.32%) and delivers 239.2V at the load.

What size aluminum wire is required for 900 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.48V (1.03%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.